CANopen Slave Communication Module IFD9503
DVP-PLC Application Manual
7
PIN 8
PIN 7
PIN 6
Baud rate
Off On Off
50k
bps
Off On On
125k
bps
On Off Off
250k
bps
On Off On
500k
bps
On On Off
800k
bps
On On On
1M
bps
z
Note:
The changed setting of the baud rate of CANopen is only valid when IFD9503 is re-powered. When
IFD9503 is operating, changing the baud rate will be invalid.
2.5
Communication Ports on IFD9503
The communication ports on IFD9503 are used for the connection the
equipment (Delta programmable logic controller, Delta AC motor drive,
Delta temperature controller, Delta servo drive, Delta human machine
interface and custom equipment).
PORT1
PORT2
1. PORT 1 PIN definition:
PORT 1 sketch
PIN
Description
1 N.C.
2 GND
3 DATA-
4 DATA+
5 N.C.
1
2
3
4
5
6
PORT1
6 N.C.
z
Note:
PORT 1 supports RS-485 communication only.
2. PORT 2 PIN definition:
PORT2 sketch
PIN
RS-232
RS-485
1 N.C.
N.C.
2 RXD
N.C.
3 TXD
DATA-
4 N.C.
N.C.
5 GND
N.C.
6 N.C.
N.C.
7 N.C.
N.C.
8 N.C.
DATA+
1
6
2
7
3
8
4
9
5
DB9 male
9 N.C.
N.C.
z
Note:
PORT 2 supports RS-232 and RS-485 communication only.