CANopen Slave Communication Module IFD9503
DVP-PLC Application Manual
26
3.6
When IFD9503 is connected to Delta DOP-A HMI
DVP-SV
DVPCOPM-SL
DVPCOM
DVP28SV
RU N
STOP
Master
CANopen
CAN+
CAN-
SHLD
GND
IFD9503
RS-232/RS-485
F1
F3
F2
COM1 COM2
Delta DOP-A HMI
1.
Setting up baud rate and communication format
z
Before connecting the HMI to the bus, first set up the baud rate to 115,200bps and
communication format to 7, E, 1; ASCII (the format is fixed; other formats will be invalid).
z
HMI as the master and IFD9503 as the slave. There are 64 virtual D devices (D0 ~ D63) in
IFD9503. CANopen master and HMI are able to map, read and write the virtual D devices in
IFD9503.
z
To adjust the baud rate, follow the steps listed below.
Set up the DIP switch SW3 of IFD9503 to custom equipment mode.
Connect IFD9503 to the bus of CANopen and enable the operation of IFD9503.
Modify the index parameter 5003/06.
5003/06 = 1
→
19,200; 7, E, 1; ASCII
5003/06 = 2
→
38,400; 7, E, 1; ASCII
5003/06 = 3
→
57,600; 7, E, 1; ASCII
5003/06 = 4
→
115,200; 7, E, 1; ASCII (Default)
Return SW3 of IFD9503 back to HMI mode and re-power IFD9503.
Adjust the baud rate of the HMI to the corresponding one.
z
When IFD9503 is connected to DOP HMI, set up the baud rate and communication format
following the steps below.