Delta Electronics. Inc.
HPH-
20KA01KAT
8
3.3.
Arc Suppression Specification
Figure 3.4 shows the waveforms and key parameters under arc condition, and Table 3.3
indicates the arc energy and adjustable parameters for user.
Figure 3.4 Arc Suppression mechanisms
Table 3.3 Arc Energy specification and adjustable parameters for User
Item
Specification
Description
Delay Time
1 to 5 µs
Adjustable delay until cutoff
output after detecting arc
Pause Time
40 to 250 µs
Adjustable time between output
cutoff and recovery
Arc Trip Voltage Level
25 to 200 V
The level to determine if arc
occurs from output
Over Arc Density Protection
1 to 99
Adjustable counter to alarm if
the a frequent arc condition
occurs within 1 second
Over Arc Number Protection
1 to 999
Adjustable counter to alarm if
the arc number is over the
setting.
Arc Energy
< 1 mJ per kW
0V
0A
Arc Occurs
Detection Circuit Activated
Arc Detected
Switching off
Detection
Time
Delay
Time
Pause
Time
Arc Voltage
Trip Level
t
1
t
2
Voltage
Current
Signal of
Switching
t
t
3
t
4
t
5
t
6
t
7
Recovery
Time
Содержание HPH-20KA01KAT
Страница 1: ...User Manual DC Power Supply Continuous 400 1000 VDC Model HPH 20KA01KAT Version Rev S 00...
Страница 13: ...Delta Electronics Inc HPH 20KA01KAT 9...
Страница 15: ...Delta Electronics Inc HPH 20KA01KAT 11...
Страница 20: ...Delta Electronics Inc HPH 20KA01KAT 16 Energy Mode Monitor 06 While output reaches setting Energy A...
Страница 22: ...Delta Electronics Inc HPH 20KA01KAT 18...
Страница 29: ...Delta Electronics Inc HPH 20KA01KAT 25 6 3 Main Menu Map Fig 6 1 Panel tree...
Страница 41: ...Delta Electronics Inc HPH 20KA01KAT 37...