Ultron HPH Series UPS
No.
Alarm Message
Possible Cause
Solution
16
INVERTER SOFT
START FAIL
1. Inverter detection is abnormal.
2. Inverter’s driver is damaged.
Contact service personnel.
17
INNER
COMMUNICATION
FAIL
Inner communication cable is not
well connected.
Contact service personnel.
18
PFC SUPERVISOR
FAIL
PFC CPU is damaged.
Contact service personnel.
19
DC BUS HIGH
SHUTDOWN
1. Output has abnormalities.
2. The UPS has internal faults.
Contact service personnel.
20
DC BUS LOW
SHUTDOWN
1. Output has abnormalities.
2. The UPS has internal faults.
Contact service personnel.
21
INPUT FUSE FAIL
Input fuse is broken.
Contact service personnel.
22
INVERTER
SUPERVISOR FAIL
Inverter CPU is damaged.
Contact service personnel.
23
PFC SOFT
START FAIL
5HFWL¿HUWXEHLVGDPDJHG
2. Driver is damaged.
Contact service personnel.
24
BYPASS PHASE
SEQUENCE FAIL
Bypass phase sequence is wrong. Please check bypass phase
sequence.
25
NTC OPEN FAIL
1. NTC is not connected well.
2. NTC line is broken.
Contact service personnel.
26
INVERTER OUTPUT
SCR SHORT
1. Inverter SCR driver is
abnormal.
2. Inverter SCR is damaged.
Contact service personnel.
27
BATTERY LOW
SHUTDOWN
Battery voltage is low.
Charge the batteries.
28
LCD error or no
response
LCD fail or communication fail or
noise interference
1. Simultaneously press the
UP
(
) and
DOWN
(
)
function keys for around 5
seconds to reset the LCD.
2. If the error still exists, contact
service personnel.
NOTE:
If all possible causes are eliminated but the alarm still appears, please contact your local
dealer or customer service.