Chapter 6 Installation and Wiring
y
When connecting the UPS to the critical loads, you must install a 3-pole EN 60947-2 cer-
WL¿HGEUHDNHUEHWZHHQWKHP3OHDVHUHIHUWRWKHWDEOHEHORZ
UPS
Suggested Protective Device
60kVA
D-Curve 125A Circuit Breaker
80kVA
D-Curve 160A Circuit Breaker
100kVA
D-Curve 200A Circuit Breaker
120kVA
D-Curve 225A Circuit Breaker
y
Check that the size, diameter, phase, and polarity of each cable that needs connecting
WRWKH836LVFRUUHFW)RUWKHVSHFL¿FDWLRQVRILQSXWRXWSXWFDEOHVDQGFLUFXLWEUHDNHUV
please refer to
Table 6-1
.
7DEOH6SHFL¿FDWLRQVRI,QSXW2XWSXW%DWWHU\&DEOHVDQG&LUFXLW%UHDNHUV
UPS
60kVA
80kVA
100kVA
120kVA
Input
Rated current at 400V
with battery charging
92A
123A
171A
183A
Recommended cable
size (R/ S/ T/ N/ PE)
35mm
2
50mm
2
95mm
2
95mm
2
Maximum cable size
(R/ S/ T/ N/ PE)
70mm
2
120mm
2
120mm
2
120mm
2
Cable lug width
23mm
28mm
28mm
28mm
Screw size
M8
M8
M8
M8
Output
Rated current at 400V
87A
116A
145A
174A
Recommended cable
size (R/ S/ T/ N/ PE)
35mm
2
50mm
2
70mm
2
95mm
2
Maximum cable size
(R/ S/ T/ N/ PE)
70mm
2
120mm
2
120mm
2
120mm
2
Cable lug width
23mm
28mm
28mm
28mm
Screw size
M8
M8
M8
M8