1 5
Chapter 3 Appearance and Mechanism
No.
Item
Description
1
Input Breaker
Controls the UPS’s input breaker and for safety protection.
2
AC Input Terminal
Block
Connects the main AC source.
3
For the UPS grounding.
4
Casters
The casters are designed for a short distance movement only.
Do not use the casters to move the UPS over a long distance.
The casters are not designed to provide long-term support for
the UPS. Please refer to
6.4 UPS Installation & Fixing
for how
WR¿UPO\¿[WKH836RQWKHJURXQG
5
Bypass Breaker
Controls the UPS’s bypass breaker. Follow customer ’s
requirement to decide whether the bypass breaker should be
installed or not.
6
Manual Bypass
Breaker
For maintenance only! Only authorized service personnel can
operate the manual bypass breaker.
7
Output Breaker
Controls the UPS’s output breaker and for safety protection.
The default is a 3-pole output breaker. An alternative of a 4-ploe
one could be installed according to customer’s requirement.
8
UPS Output
Terminal Block
Connects the critical loads.
9
For the critical loads’ grounding.
10
Levelers
The levelers are designed to provide long-term support for the
UPS.
11
DC Fans
Cool and ventilate the UPS.
12
Parallel Ports
For UPS parallel usage. For detailed information, please refer
to
Chapter 5: Communication Interfaces
.
13
SMART Slot
Connects SNMP/ Relay I/O/ ModBus card. For detailed
information, please refer to
Chapter 5: Communication
Interfaces
.
14
MINI Slot
Connects Mini SNMP/ Mini Relay I/O/ Mini USB/ Mini Mod-
Bus/ Mini TVSS card. For detailed information, please refer to
Chapter 5: Communication Interfaces
.
15
External Battery
Temperature
Ports
Connect an external battery cabinet. For detailed information,
please refer to
Chapter 5: Communication Interfaces
.