Ultron HPH Series UPS
y
Dual Input (Single Unit)
When there are two AC power sources, single unit wiring procedures are as follows.
1
3OHDVHFRQWDFWTXDOL¿HGVHUYLFHSHUVRQQHOWRPRGLI\WKH836LQWRGXDOLQSXW3OHDVH
QRWHWKDWRQO\TXDOL¿HGVHUYLFHSHUVRQQHOFDQPRGLI\VLQJOHLQSXWGXDOLQSXWVHWXS
2
Please follow steps
1
a
5
stated in section
Single Input (Single Unit)
.
3
Ensure that the input breaker and bypass breaker are in the
OFF
position.
4
According to the capacity and the model of your UPS, select proper input and output
cables. Please refer to
Table 6-1
.
5
Connect the main AC source/ bypass source/ output/ external battery cabinet cables
to the wiring terminal block (please refer to
Figure 6-12~6-14
).
NOTE:
Regarding
Figure 6-12~6-14
HDFK¿JXUHUHSUHVHQWVWKDWWKHXWLOLW\$&SRZHULV
the TN system and a 3-pole protective device is installed between the UPS and
the utility AC power. If your utility AC power is the TT system, please install a 4-pole
protective device between the UPS and the utility AC power.
6
Ground the UPS.
(Figure 6-12: 60kVA Model - Single Unit Dual Input Wiring Diagram)
R
S
T
R
S
T
R
S
T
N
N
N
AC INPUT
BYPASS INPUT
UPS OUTPUT
AC INPUT
BYPASS INPUT
UPS OUTPUT
I
O
ON
OFF
I
O
ON
OFF
I
O
ON
OFF
I
O
ON
OFF
I
O
ON
OFF
I
O
ON
OFF
I
O
ON
OFF
I
O
ON
OFF
I
O
ON
OFF
INPUT BREAKER
R
BYPASS BREAKER
MANUAL BYPASS
BREAKER
OUTPUT BREAKER
S
T
N
R
S
T
R
S
T
R
S
T
I
O
ON
OFF
I
O
ON
OFF
I
O
ON
OFF
240V DC
240V DC
BATTERY INPUT
N
T
S
R
N
N
T
S
R
T
S
R
-
N
+
For the UPS
grounding
3-pole
protective
device
3-pole
protective
device
3-pole
protective
device
Connects the
main AC source
Connects the
bypass source
Connects the external
battery cabinet
Connects the
critical loads
For the critical
loads’ grounding ( )
For the external
battery cabinet’s
grounding ( )
3-pole
protective
device
(Front)
(Rear)