Load Cell Module DVP02LC-SL
DVP-PLC Operation Manual
Hardware
Wiring
y
Connecting DVP20SX2 with the two modules:
DVP20SX
DVP02LC
DVP04DA
y
Wiring for load cell: Connect two 4-wire load cells in parallel, and then to CH1 on DVP02LC-SL.
CH1
CH2
DVP02LC
Load cell
Load cell
Setting up Parameters
y
Parameters for DVP02LC-SL:
Parameter
Set value
Explanation
Eigenvalue
2 (mV/V)
2 mV/V is the eigenvalue spec. for the load cell.
Measuring time
10 (ms)
--
CH1 average times
50
--
CH1 max. weight
32,767
The max. weight is limited to 32,767.
CH2 net or gross weight
Disabled
CH2 function is disabled.
Note: Parameters that are not set up will use the software default setting.
y
Correction
by
software
1. Set the eigenvalue (characteristic value) of the load cell to 2 mV/V and the measuring time to