Load Cell Module DVP02LC-SL
DVP-PLC Operation Manual
bit
Status
bit3
H’0008
CH2 exceeds max. weight (overload)
bit4
H’0010
CH1 measured value is stable.
bit5
H’0020
CH2 measured value is stable.
bit6 ~ 15
Reserved
C R # 5 1 :
Error code
Explanations:
Bit
Content
Error
Bit
Content
Error
b0 K1
(H’0001)
Power supply
abnormality
b1 K2
(H’0002)
Hardware
abnormality
b2
K4 (H’0004)
CH1 conversion error
b3
K8 (H’0008)
CH1 SEN voltage
error
b4
K16 (H’0010) CH2 conversion error
b5 K32 (H’0020)
CH2 SEN voltage
error
b6 ~ b15 K64 (H’0040)
Reserved
Note: Every error status is determined by its corresponding bit, so there might be more than
2 error statuses occurring at the same time. 0 refers to no error; 1 refers to error
occurring.
C R # 5 2 , 53 ,5 4 , 5 5:
Communication format for RS-232 and RS-485
Explanations:
bit15
bit14 ~ bit8 bit7
bit6
bit5
bit4
bit3
bit2
bit1
bit0
ACSII/RTU Reserved
Baudrate
Data
length
Stop bit
Parity
Description
bit15 ACSII/RTU
0 ACSII 1 RTU
0 9,600 bps
1 19,200 bps
2 38,400 bps
3 57,600 bps
bit7 ~ bit4 Baudrate
4 115,200 bps
5 Else none
bit3
Data length (RTU = 8 bits)
0 7 1 8
bit2 Stop
bit
0 1 bit
1 2 bits
0 Even 1 Odd
bit1 ~ bit0 Parity
2 None 3 None
Example: If you would like to communication format for RS-232 to be “115200, 7, E, 1, ASCII” set
CR#53 to “H’0400”.