Load Cell Module DVP02LC-SL
DVP-PLC Operation Manual
Gross/Net:
Corresponds to the value in CR#7. Scroll down to select displaying the gross weight or net weight.
Tare
weight:
Corresponds to the value in CR#8 and CR#9. Enter the tare weight here, or click “Read TW” to set
it up. The range is -32,768 to 32,767, and the default setting is 0.
Read
TW:
Corresponds to the value in CR#6. Click “Read TW” to take the average value of each channel as
the tare weight.
Average
times:
Corresponds to the value in CR#10 and CR#11. The range is 1 to 100, and the default setting is
10.
Maximum
weight:
Corresponds to the value in CR#35 and CR#36. Enter the maximum weight here. When the
measured value exceeds this weight, an error status will be displayed. The range is -32,768 to
32,767, and the default setting is 32,767.
Unit of measurement:
Corresponds to CR#22 and CR#23 for CH1 and CR#24 and CR#25 for CH2. You can enter a unit
here for the user’s reference. Maximum 4 characters are allowed in this column. The default
setting is Kg.
Standstill
times:
The times of standstill checks, corresponding to the value in CR#16 and CR#17. Enter the times
here. The range is 1 to 500, and the default setting is 5.
Standstill
range:
The range for standstill check, corresponding to the value in CR#18 and CR#19. Enter the range
(1 to 10,000) here. The default setting is 10.
Zero
band:
The upper and lower limits for the zero point check. The upper limit for CH1 corresponds to the
value in CR#37, and the lower limit corresponds to the value in CR#39. The upper limit for CH2
corresponds to the value in CR#38, and the lower limit corresponds to the value in CR#40. When
the weight measured is within the range, the status code will be set to
“
zero bit
"
indicating that it
is currently in empty status now. Enter the upper and lower limits here. The range is K-32,768 to
K32,767, and the default setting is -10 to 10.
Filter ratio setting
The filter percentage, corresponding to the value in CR#43 and CR#44. The range is 1 to 5. The
average weight after being filtered will be displayed as the filter average values for CH1 and CH2
on the toolbar, or you can check CR#45 and CR#46 for the filter average value. The default setting
is 2.