Chapter 12 Description of Parameter Settings
CT2000 Series
12.2-00-9
6. Set up the speed estimator related parameters
I/F Mode Current Command / Low-speed Current Command under PMSVC
Control
Factory
Setting:40
Settings 0~150% of motor’s rated current
The parameter is the current command of the drive in low-speed area (low-speed area:
frequency command < Pr10-39).
When it is stalling on heavy duty start-up or forward/reverse with load, adjust the parameter
(to increase it). If inrush current too higher to cause oc stall, then decrease it.
PM FOC Sensorless Speed Estimator Bandwidth
Factory Setting: 5.00
Settings 0.00~600.00Hz
The parameter is speed estimator bandwidth. Adjust the parameter will influence the stability
and the accuracy of speed for motor.
If there is low frequency vibrates (the waveform is similar to sine wave) during the process,
then increase the bandwidth. If there is high frequency vibrates (the waveform vibrates
extremely and is like spur), then decrease the bandwidth.
PM Sensorless Observer Low-pass Filter Gain
Factory Setting: 1.00
Settings 0.00~655.35
Adjust the parameter will influence the speed estimator’s speed of response.
If there is low frequency vibrates (the waveform is similar to sine wave) during the process,
then increase the gain. If there is high frequency vibrates (the waveform vibrates extremely
and is like spur), then decrease the gain.
AMR (Kp)
Factory Setting: 1.00
Settings 0.00~3.00
AMR (Ki)
Factory Setting: 0.20
Settings 0.00~3.00
Active Magnetic regulator--- Kp and Ki. These two parameters will influence magnetic flux
control of field weakening region.
Increase the parameter if the input power has rapid change (ex. unstable electrical grid
makes voltage be insufficient in a sudden) while enter the field weakening region, and ACR
diverges to cause oc (ex. during the application of Press, there are other Press is working,
and DC BUS decreases extremely in a sudden). If Id has spur and cause high frequency
noise of output current to be too big, then decrease the parameter to lower the noise, but
this also might cause a slow response.
Содержание CT2000 Series
Страница 5: ...Chapter 1 Introduction CT2000 Series 1 2 Model Name VFD 750 CT 43 F 00 A6 Serial Number...
Страница 22: ...Chapter 1 Introduction CT2000 Series 1 19 Digital Keypad KPC CC01 KPC CE01 Unit mm inch...
Страница 23: ...Chapter 1 Introduction CT2000 Series 1 20 This page intentionally left blank...
Страница 41: ...Chapter 4 Wiring CT2000 Series 4 6 This page intentionally left blank...
Страница 71: ...Chapter 7 Optional Accessories CT2000 Series 7 18 Wall Mounting Embedded Mounting...
Страница 87: ...Chapter 8 Optional Cards CT2000 Series 8 8 PG Card intallation...
Страница 88: ...Chapter 8 Optional Cards CT2000 Series 8 9 Disconneting the extension card...
Страница 92: ...Chapter 8 Optional Cards CT2000 Series 8 13 PG2 Wiring Diagram...
Страница 95: ...Chapter 8 Optional Cards CT2000 Series 8 16 PG2 Wiring Diagram...
Страница 117: ...Chapter 8 Optional Cards CT2000 Series 8 38 This page intentionally left blank...
Страница 121: ...Chapter 9 Specifications CT2000 Series 9 4 Frame B 370 0 140 0 Frame C 180 0 500 0 Frame D 180 0 660 0 Figure 1...
Страница 259: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 11...
Страница 260: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 12...
Страница 263: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 15...
Страница 266: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 18...
Страница 397: ...Chapter 13 Warning Codes CT2000 Series 13 8 This page intentionally left blank...
Страница 407: ...Chapter 14 Fault Codes and Descriptions CT2000 Series 14 10 This page intentionally left blank...
Страница 489: ...Chapter 16 PLC Function CT2000 Series 16 48 LD X1 Load Contact a of X1 OUT Y1 Drive Y1 coil...
Страница 591: ...Chapter 16 PLC Function CT2000 Series 16 150 Step 3 Physical configuration CT2000 Step 4 Write to PLC program...
Страница 592: ...Chapter 16 PLC Function CT2000 Series 16 151...
Страница 594: ...Chapter 16 PLC Function CT2000 Series 16 153...
Страница 597: ...Chapter 16 PLC Function CT2000 Series 16 156 This page intentionally left blank...
Страница 633: ...Chapter 19 EMC Standard Installation Guide CT2000 Series 19 20 This page intentionally left blank...