Chapter 12 Description of Parameter Settings
CT2000 Series
12.1-08-3
8. Pr.08-01-08-03 will be set as required
8.1 If there is no vibration in the system, increase Pr.08-01(Proportional Gain (P))
8.2 If there is no vibration in the system, reduce Pr.08-02(Integral Time (I))
8.3 If there is no vibration in the system, increase Pr.08-03(Differential Time(D))
Refer to Pr.08-00 to 08-21 for PID parameters settings.
Proportional Gain (P)
Factory
Setting:1.0
Settings 0.0~500.0
It is used to eliminate the system error. It is usually used to decrease the error and get the faster
response speed. But if setting too large value in Pr.08-01, it may cause the system oscillation and
instability.
If the other two gains (I and D) are set to zero, proportional control is the only one effective.
Integral Time (I)
Factory
Setting:1.00
Settings 0.00~100.00 sec
0.00: Disable
The integral controller is used to eliminate the error during stable system. The integral control
doesn’t stop working until error is 0. The integral is acted by the integral time. The smaller integral
time is set, the stronger integral action will be. It is helpful to reduce overshoot and oscillation to
make a stable system. At this moment, the decreasing error will be slow. The integral control is
often used with other two controls to become PI controller or PID controller.
This parameter is used to set the integral time of I controller. When the integral time is long, it will
have small gain of I controller, the slower response and bad external control. When the integral
time is short, it will have large gain of I controller, the faster response and rapid external control.
When the integral time is too small, it may cause system oscillation.
If the integral time is set as 0.00, Pr.08-02 will be disabled.
Derivative Control (D)
Factory
Setting:0.00
Settings 0.00~1.00 sec
The differential controller is used to show the change of system error and it is helpful to preview
the change of error. So the differential controller can be used to eliminate the error to improve
system state. With the suitable differential time, it can reduce overshoot and shorten adjustment
time. However, the differential operation will increase the noise interference. Please note that
too large differential will cause big noise interference. Besides, the differential shows the change
and the output of the differential will be 0 when there is no change. Therefore, the differential
control can’t be used independently. It needs to be used with other two controllers to make a PD
controller or PID controller.
This parameter can be used to set the gain of D controller to decide the response of error change.
The suitable differential time can reduce the overshoot of P and I controller to decrease the
oscillation and have a stable system. But too long differential time may cause system oscillation.
The differential controller acts for the change of error and can’t reduce the interference. It is not
recommended to use this function in the serious interference.
Содержание CT2000 Series
Страница 5: ...Chapter 1 Introduction CT2000 Series 1 2 Model Name VFD 750 CT 43 F 00 A6 Serial Number...
Страница 22: ...Chapter 1 Introduction CT2000 Series 1 19 Digital Keypad KPC CC01 KPC CE01 Unit mm inch...
Страница 23: ...Chapter 1 Introduction CT2000 Series 1 20 This page intentionally left blank...
Страница 41: ...Chapter 4 Wiring CT2000 Series 4 6 This page intentionally left blank...
Страница 71: ...Chapter 7 Optional Accessories CT2000 Series 7 18 Wall Mounting Embedded Mounting...
Страница 87: ...Chapter 8 Optional Cards CT2000 Series 8 8 PG Card intallation...
Страница 88: ...Chapter 8 Optional Cards CT2000 Series 8 9 Disconneting the extension card...
Страница 92: ...Chapter 8 Optional Cards CT2000 Series 8 13 PG2 Wiring Diagram...
Страница 95: ...Chapter 8 Optional Cards CT2000 Series 8 16 PG2 Wiring Diagram...
Страница 117: ...Chapter 8 Optional Cards CT2000 Series 8 38 This page intentionally left blank...
Страница 121: ...Chapter 9 Specifications CT2000 Series 9 4 Frame B 370 0 140 0 Frame C 180 0 500 0 Frame D 180 0 660 0 Figure 1...
Страница 259: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 11...
Страница 260: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 12...
Страница 263: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 15...
Страница 266: ...Chapter 12 Description of Parameter Settings CT2000 Series 12 1 03 18...
Страница 397: ...Chapter 13 Warning Codes CT2000 Series 13 8 This page intentionally left blank...
Страница 407: ...Chapter 14 Fault Codes and Descriptions CT2000 Series 14 10 This page intentionally left blank...
Страница 489: ...Chapter 16 PLC Function CT2000 Series 16 48 LD X1 Load Contact a of X1 OUT Y1 Drive Y1 coil...
Страница 591: ...Chapter 16 PLC Function CT2000 Series 16 150 Step 3 Physical configuration CT2000 Step 4 Write to PLC program...
Страница 592: ...Chapter 16 PLC Function CT2000 Series 16 151...
Страница 594: ...Chapter 16 PLC Function CT2000 Series 16 153...
Страница 597: ...Chapter 16 PLC Function CT2000 Series 16 156 This page intentionally left blank...
Страница 633: ...Chapter 19 EMC Standard Installation Guide CT2000 Series 19 20 This page intentionally left blank...