ASDA-B2-F Troubleshooting
September, 2015
9-7
9
AL011
Encoder error
Cleared after re-power on
Causes
Checking Method
Corrective Actions
Wrong wiring of the encoder Check if the wiring follows the
suggested wiring in the user manual.
Correct wiring
The encoder is loose.
Check the CN2 connector of the drive
and the encoder connector.
Install the encoder again.
Bad connection of the
encoder
Check if the connection between CN2
connector of the drive and the encoder
of the servo motor is loose.
Reconnect the wiring.
The encoder is damaged.
Check if the motor is damaged.
Change the motor.
AL012
Adjustment error
N/A
Causes
Checking Method
Corrective Actions
Abnormal current adjustment Reset power supply.
If the error still occurs after reset,
send the drive back to the
distributors or contact with Delta.
AL013
Emergency stop
Automatically cleared after DI.EMGS is OFF
Causes
Checking Method
Corrective Actions
The emergency stop button
is pressed.
Check if the emergency stop button is
enabled.
Release emergency stop button.
AL014
Reverse limit error
Cleared by DI.ARST, Servo Off or after motor
operates backwards
Causes
Checking Method
Corrective Actions
Reverse limit switch is
activated.
Check if the reverse limit switch is
activated.
Release the reverse limit
switch.(e.g. motor operates
backwards)
AL015
Forward limit error
Cleared by DI.ARST, Servo Off or after motor
operates backwards
Causes
Checking Method
Corrective Actions
Forward limit switch is
activated.
Check if the forward limit switch is
activated.
Release the forward limit
switch.(e.g. motor operates
backwards)
AL016
IGBT overheat
Cleared by DI.ARST
Causes
Checking Method
Corrective Actions
Over the rated loading of the
drive and continuously
excessive using
Check if the drive is overloading or the
motor current is too high.
Increase the motor capacity or
reduce the load.
The drive output is
short-circuited.
Check the drive output wiring.
Correct wiring.
Содержание ASD-B2-0121-F
Страница 3: ...September 2015 This page is intentionally left blank...
Страница 9: ...VI September 2015 This page is intentionally left blank...
Страница 17: ...Inspection and Model Explanation ASDA B2 F 1 8 September 2015 1 This page is intentionally left blank...
Страница 29: ...Installation ASDA B2 F 2 12 September 2015 2 This page is intentionally left blank...
Страница 117: ...Control Mode of Operation ASDA B2 F 6 28 September 2015 6 This page is intentionally left blank...
Страница 185: ...Parameters ASDA B2 F 7 68 September 2015 7 This page is intentionally left blank...
Страница 199: ...Communications ASDA B2 F 8 14 September 2015 8...
Страница 201: ...Communications ASDA B2 F 8 16 September 2015 8 This page is intentionally left blank...
Страница 217: ...Troubleshooting ASDA B2 F 9 16 September 2015 9 This page is intentionally left blank...
Страница 239: ...Absolute System ASDA B2 F 10 22 September 2015 10 This page is intentionally left blank...
Страница 265: ...Appendix A Specifications ASDA B2 F A 26 September 2015 A This page is intentionally left blank...
Страница 287: ...Appendix C Basic Inspection and Maintenance ASDA B2 F C 4 September 2015 C This page is intentionally left blank...