Chapter 5 Parameters
|
VFD-S Series
Revision August 2008, SE09, SW V2.61
5-7
Group 5 Multi-Step Speed and PLC Parameters
Pr. Explanation
Settings
Factory
Setting
NOTE
5-00 1st Step Speed Freq.
d0.0 to d400 Hz
d0.0
5-01 2nd Step Speed Freq.
d0.0 to d400 Hz
d0.0
5-02 3rd Step Speed Freq.
d0.0 to d400 Hz
d0.0
5-03 4th Step Speed Freq.
d0.0 to d400 Hz
d0.0
5-04 5th Step Speed Freq.
d0.0 to d400 Hz
d0.0
5-05 6th Step Speed Freq.
d0.0 to d400 Hz
d0.0
5-06 7th Step Speed Freq.
d0.0 to d400 Hz
d0.0
5-07 PLC
Mode
d0: Disable PLC Operation
d1: Execute one program cycle
d2: Continuously execute program
cycles
d3: Execute one program cycle step
by step
d4: Continuously execute one
program cycle step by step
d5: Disable PLC operation, but can
set direction of 1st speed to 7th
speed
d0
5-08 PLC Forward/ Reverse Motion
d0 to d255 (0: FWD 1: REV)
d0
5-09 Time Duration of Master Speed
d0 to d65500 Sec
d0
5-10 Time Duration of 1st Step Speed
d0 to d65500 Sec
d0
5-11 Time Duration of 2nd Step Speed
d0 to d65500 Sec
d0
5-12 Time Duration of 3rd Step Speed
d0 to d65500 Sec
d0
5-13 Time Duration of 4th Step Speed
d0 to d65500 Sec
d0
5-14 Time Duration of 5th Step Speed
d0 to d65500 Sec
d0
5-15 Time Duration of 6th Step Speed
d0 to d65500 Sec
d0
5-16 Time Duration of 7th Step Speed
d0 to d65500 Sec
d0
Group 6 Protection Parameters
Pr. Explanation
Settings
Factory
Setting
NOTE
6-00 Over-Voltage
Stall
Prevention
d0: Disable
d1: Enable
d1
115V/230V series: d350 to d410V
d390
6-01
Over-Voltage Stall Prevention Level
460V series: d700 to d820V
d780
6-02 Over-Current Stall Prevention Level
d20 to d150%
d130
d0: Disabled
d1: Enabled during constant speed
operation. After the over-torque
is detected, keep running until
OL1 or OL occurs.
d2: Enabled during constant speed
operation. After the over-torque
is detected, stop running.
6-03 Over-Torque Detection Mode
d3: Enabled during running and
continues before Continuous
Output Time Limit (Pr.6-05) is
reached.
d0
Содержание Network Device VFD-S
Страница 1: ......
Страница 2: ......
Страница 3: ......
Страница 15: ...Chapter 1 Introduction VFD S Series 1 6 Revision August 2008 SE09 SW V2 61 This page intentionally left blank...
Страница 53: ...Chapter 3 Start Up VFD S Series 3 4 Revision August 2008 SE09 SW V2 61 This page intentionally left blank...
Страница 177: ...Appendix B Accessories VFD S Series B 20 Revision August 2008 SE09 SW V2 61 This page intentionally left blank...