Chapter 3 Start Up
3.1 Preparations before Start-up
Carefully check the following items before proceeding.
Make sure that the wiring is correct. In particular, check that the output terminals U/T1,
V/T2, W/T3 are NOT connected to power and that the drive is well grounded.
Verify that there are no short-circuits between terminals and from terminals to ground or
mains power.
Check for loose terminals, connectors or screws.
Verify that no other equipment is connected to the AC motor.
Make sure that all switches are OFF before applying power to ensure that the AC motor
drive doesn’t start running and there is no abnormal operation after applying power.
Make sure that the front cover is correctly installed before applying power.
Do NOT operate the AC motor drive with humid hands.
Check the following items after applying power: The display without digital keypad should
be as following.
-The keypad should light up as follows (normal status with no error)
RUN
FWD
REV
STOP
MIN. MAX.
RUN
STOP/RESET
MODE
PROG
DATA
- If the drive has built-in fan, it should run.
When power is ON,
LEDs “STOP” and “FWD”
should light up. The
display will show “F60.0”.
Содержание Network Device VFD-S
Страница 1: ......
Страница 2: ......
Страница 3: ......
Страница 15: ...Chapter 1 Introduction VFD S Series 1 6 Revision August 2008 SE09 SW V2 61 This page intentionally left blank...
Страница 53: ...Chapter 3 Start Up VFD S Series 3 4 Revision August 2008 SE09 SW V2 61 This page intentionally left blank...
Страница 177: ...Appendix B Accessories VFD S Series B 20 Revision August 2008 SE09 SW V2 61 This page intentionally left blank...