Chapter 5 Parameters
|
VFD-S Series
5-58
Revision August 2008, SE09, SW V2.61
Group 8: Special Parameters
8-00
DC Brake Current Level
Unit: 1
Settings
d0 to d30%
Factory Setting: d0
This parameter determines the level of DC Brake Voltage Level output to the motor during
start-up and stopping. When setting DC Brake Voltage, the Maximum Output Voltage (Pr.1-
02) is regarded as 100%. It is recommended to start with a low DC Brake Voltage Level and
then increase until proper holding torque has been attained.
8-01
DC Brake Time during Start-up
Unit: 0.1
Settings
d0.0 to d60.0 sec
Factory Setting: d0.0
This parameter determines the duration of time that the DC Brake Current will be applied to
the motor during the AC drive start-up.
8-02
DC Brake Time during Stopping
Unit: 0.1
Settings
d0.0 to d60.0 sec
Factory Setting: d0.0
This parameter determines the duration of time that the DC brake voltage will be applied to
the motor during stopping. If stopping with DC Brake is desired, then Pr.2-02 must be set to
RAMP stop (d0).
8-03
Start-Point for DC Brake
Unit: 0.1
Settings
d0.0 to d400Hz
Factory Setting: d0.0
This parameter determines the frequency when DC Brake will begin during deceleration.
Operation
Command
ON
OFF
01-05
08-03
Output Frequency
Minimum Output
Frequency
Start-Point for
DC Brake
Time during
Stopping
DC Brake Voltage %
Time
08-01
08-02
Содержание Network Device VFD-S
Страница 1: ......
Страница 2: ......
Страница 3: ......
Страница 15: ...Chapter 1 Introduction VFD S Series 1 6 Revision August 2008 SE09 SW V2 61 This page intentionally left blank...
Страница 53: ...Chapter 3 Start Up VFD S Series 3 4 Revision August 2008 SE09 SW V2 61 This page intentionally left blank...
Страница 177: ...Appendix B Accessories VFD S Series B 20 Revision August 2008 SE09 SW V2 61 This page intentionally left blank...