Not every input can be used for both functions.
Level detection
The I/O modules AAST, ADFT, AMDT, DIOT, and IOIT OTPT have
digital inputs for level detection.
For reliable detection, the input signal must have a "low" level ran-
ging from 0 ... 1.5 V, a "high" level ranging from 3.5 ... 90 V and a
minimum pulse width of 1 ms. A maximum of 50 signal changes per
second (maximum signal frequency) can be recorded.
Frequency measurement/pulse counting
The I/O modules ADFT, and AMDT DIOT have digital inputs for fre-
quency measurement/pulse counting.
For reliable detection, the input signal must have a "low" level ran-
ging from 0 ... 1.5 V and a "high" level ranging from 3.5 ... 90 V. The
maximum measurable signal frequencies are 50 kHz for the ADFT
and AMDT module and 30 kHz for the DIOT module.
209
Delphin Technology AG
Dezember 2015
Profi
Message Manual
Содержание ProfiMessage
Страница 1: ......
Страница 31: ...ProfiMessage 3 5 4 ADIT 31 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Страница 32: ...ProfiMessage 3 5 5 ADVT 3 5 6 AMDT 32 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Страница 33: ...ProfiMessage 3 5 7 DIOT 3 5 8 IOIT 33 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Страница 234: ...ProfiMessage Block diagram for an analogue input signal 234 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Страница 312: ...ProfiMessage 11 Appendix 11 1 ISO 9001 certificate 312 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Страница 313: ...ProfiMessage 11 2 EC declaration on conformity 313 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Страница 314: ...ProfiMessage 314 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Страница 322: ......