![Delphin ProfiMessage Скачать руководство пользователя страница 113](http://html1.mh-extra.com/html/delphin/profimessage/profimessage_hardware-manual_2471098113.webp)
Profi
Message
Generate intermediate values
: When enabled, results are also output between
reset events immediately following their calculation, (without being reset to zero).
4.7.9
Channel group
Use channel groups to group related or interdependent channels. Any number of
channel groups may be created. If required, a channel can be linked to more than
one group (linked channels: refer to
Configuring software channels).
4.7.10
Linearisation
Linearisation enables an additional conversion to be performed on a channel's val-
ues. An advantage of this feature is that the channel's original values remain avail-
able with the conversion being performed in a "new" channel.
The available options are identical to those for a global table. This dialogue enables
either a conversion function to be set for this channel (
Table type: local table
) or
the use of a global linearisation function (
Global table
) which has been set up via
the
Global linearisation table
option in the device's context menu.
Settings for all dialogues: Sensor
Method
1. Select a table type.
For external tables, then select a table; for an internal table, create a table via
the
Table
tab that is then displayed.
2. Select a source.
3. Set up a table if necessary (
Table
tab).
A table can be imported instead of creating a new one:
Import
.
Mode
: There is a choice of modes
l
Offset
An offset shifts the curve by a fixed value, for example the given value is
added to the measurement value.
l
Offset and slope
Allows a shifting of the curve and an increase in its slope.
l
Quadratic
Generates a quadratic curve through the given points to linearise the meas-
ured values.
l
Linear interpolation
Set a table for converting measured values into display values. Linear inter-
polation takes place between the given points.
l
Spline interpolation
113
Delphin Technology AG
Dezember 2015
Profi
Message Manual
Содержание ProfiMessage
Страница 1: ......
Страница 31: ...ProfiMessage 3 5 4 ADIT 31 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Страница 32: ...ProfiMessage 3 5 5 ADVT 3 5 6 AMDT 32 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Страница 33: ...ProfiMessage 3 5 7 DIOT 3 5 8 IOIT 33 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Страница 234: ...ProfiMessage Block diagram for an analogue input signal 234 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Страница 312: ...ProfiMessage 11 Appendix 11 1 ISO 9001 certificate 312 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Страница 313: ...ProfiMessage 11 2 EC declaration on conformity 313 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Страница 314: ...ProfiMessage 314 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Страница 322: ......