Chapter 2 - Planning
2.7.6
Video cable
Correct system startup and operation of the Honeywell-based Dell R330XL server platform requires
industry standard VESA DDC interface to the monitor. If either a monitor or video cable that does not
support DDC is attached to the server platform, the display generator defaults to a resolution, which
precludes communication with the system software and stops startup. To determine if a cable is DDC
compatible, ensure that pins 5, 9, and 12 of the HD15 connector are wired. The IS supplied cable
(51196742-200) is DDC compatible.
2.8
Industrial regulatory compliance
The compliance specifications in this section apply to cabinet installations.
WARNING
Honeywell does not claim Safety Compliance or Electromagnetic Compatibility (EMC)
Compliance for system equipment configurations that have not been described in this guide as
standard system configurations. Any equipment configuration other than that described in this
publication decertifies the Safety and EMC compliance of this product.
l
l
2.8.1
Electromagnetic Compatibility
The following table provides the Electromagnetic Compatibility (EMC) specifications (Industrial
Regulatory) for European community.
Element
Description
Emissions
EN 61326-1:2006 (Industrial Locations, CISPR 11, Class A)
Immunity
EN 61326-1:2006 (Industrial Locations)
ATTENTION
The following formula is a proximity guideline, for use of Portable Transceivers (walkie-talkies) in
the frequency range of 80MHz to 1GHz.
D > 0.30*√ {P} (D must be greater than 0.30 multiplied by the square root of P)
D = Distance from equipment, in meters.
P = Power Output of the Portable Transceivers (walkie-talkies), in Watts.
Examples:
P = 10 Watts, D > 0.949 meters
P = 5 Watts, D > 0.671 meters
P = 1 Watt, D > 0.300 meters
Electrical cables, which are routed external to the equipment, must be fully shielded cables (360
degree metallic shielding), to comply with the above EMC standards.
- 23 -