Troubleshooting
C
An individual component is not
operating as expected.
Component may not have power or may not
be firmly seated.
Ensure that the component is receiving power
(power LED should be on) and the component is
firmly seated.
Pins on the component or the backplane
might be damaged.
Remove the component from the chassis and
inspect the pins on the blade and inside the chassis.
Do not reinstall if the pins on either component are
damaged, as this could damage pins on other
components. Replace parts as required.
The component might have failed.
Enter the tempshow and sensorShow commands to
determine the component status. If the component
is a CP blade or port blade, enter the slotShow
command to determine the status. Replace the
component as necessary
TABLE 26
Troubleshooting the PowerConnect B-DCX-4S
(Continued)
Issue
Possible cause
Recommended action