Troubleshooting
85
7
Troubleshooting
Troubleshooting list
Table 42. Troubleshooting list
Issue description
Trigger event for amber LED
(MC/IM/BC)
Root cause
Troubleshooting step
Fan fail (keeps 100% duty)
1
Check HTPB.
2
Check G5.5 FW version in
IM/MC/BC.
3
Check "llcDebug" command.
BC Power LED amber
• For I
2
C communication
and MOSFET failure, BC
dumps EEPROM log.
• For FPGA configuration
failed, BC may rebooting
again and again.
1
MAC address missed or
incorrect.
2
Ethernet link is down.
3
Wrong fan table file.
4
FPGA image is wrong.
5
FPGA configuration
failed.
6
Mosfet failed.
7
I
2
C communication
failed.
1
Ensure fan table and FPGA
image s correct.
2
LAN connection is fine.
3
Ensure MAC address is correct
and present.
4
Ensure there is no HW
damage.
Fan Zone 1 fail LED amber • If 1 fan fails, BC will
move to fan table C.
• If 2 fan fails, BC will
move to fan table D and
fan will rotate on 100%
PWM.
1 or more than 1 fans
become absent from left
group of 6 fans (fan no:
1~6).
Ensure all fans insert in fan wall
properly.
Fan Zone 2 fail LED amber • If 1 fan fails, BC will
move to fan table C.
• If 2 fan fails, BC will
move to fan table D and
fan will rotate on 100%
PWM.
1 or more than 1 fans
become absent from right
group of 6 fans (fan no:
7~12).
Ensure all fans insert in fan wall
properly.
Содержание DSS 9000
Страница 43: ...Bus bar overview 32 Figure 40 Bus bar bottom P positive red Figure 41 Bus bar bottom N negative black ...
Страница 65: ...Installing and removing system components 54 Figure 64 Removing the fan module ...
Страница 72: ...61 Installing and removing system components Figure 72 Securing a cable with a cable clip ...
Страница 79: ...Installing and removing system components 68 Figure 80 Installing the BC ...