Site requirements
This table lists the ES30 and FS15 site requirements. See
on page 130 for hardware specifications information.
Table 2 ES30 and FS15 site requirements
Requirement
ES30 expansion shelf
Vertical Space in
Standard 19", 4-post
Rack
3U. Do not use a two-post rack. See the slide rail and installation
documentation in the packaging for installing in a rack.
Air Conditioning
Air conditioning that can cope with the maximum BTU/hr thermal
rating.
Temperature
Controls
Adequate temperature control with a gradient (change) not to exceed
30° C in an hour.
Front Bezel
Clearance
1.56 inches (4.0 cm) of unobstructed clearance.
Back Panel
Clearance
5 inches (12.7 cm) of unobstructed clearance.
Airflow
In a closed or multi-unit rack, ensure that the unit has adequate airflow.
If the equipment is mounted in an enclosed (as opposed to a four-post
open rack), the front and rear doors should have 65% minimum open
area for airflow. Whether in an open or enclosed rack, use filler panels
to prevent hot air recirculation. The rack design and installation should
take into consideration the maximum ambient operating temperature of
the equipment, which is 35° C.
Power/ Grounding
Two single-phase AC power outlets with an earth ground conductor
(safety ground). A safe electrical earth connection must be provided to
each power cord. Voltage should be 100-120 VAC or 200-240 VAC; 50
or 60 Hz. Use only with branch circuits protected by a minimum 15A
overcurrent protector. Plug the two power cords into separate branch
circuit supplies for redundancy.
Licensing
The appropriate capacity license is required for any added shelf. There are four tiers of
storage—active, archive, cache, and cloud. A license is purchased and applied to one
of these tiers.
Note
Only Data Domain Extended Retention (ER) systems have archive tier storage.
Note
Only Data Domain DD6300, DD6800 and DD9300 systems configured with SSDs or
those systems configured with a FS15 shelf have cache tier storage.
Shelf Installation Overview
10
Data Domain ES30 Expansion Shelf and FS15 SSD Shelf
Hardware Guide
Содержание Data Domain ES30 Expansion Shelf
Страница 1: ...Dell EMC Data Domain ES30 Expansion Shelf and FS15 SSD Shelf Hardware Guide 302 002 104 REV 04 ...
Страница 8: ...Revision history 8 Data Domain ES30 Expansion Shelf and FS15 SSD Shelf Hardware Guide ...
Страница 16: ...Shelf Installation Overview 16 Data Domain ES30 Expansion Shelf and FS15 SSD Shelf Hardware Guide ...
Страница 37: ...Figure 10 Recommended cabling for DD990 integrated with Avamar Installing the Shelves DD990 cabling 37 ...
Страница 43: ...Figure 13 Recommended DD2500 cabling Installing the Shelves DD2500 cabling 43 ...
Страница 49: ...Figure 15 Recommended DD4200 cabling Installing the Shelves DD4200 DD4500 and DD7200 cabling 49 ...
Страница 53: ...Figure 19 Recommended DD4500 cabling Installing the Shelves DD4200 DD4500 and DD7200 cabling 53 ...
Страница 57: ...Figure 23 Recommended DD7200 cabling Installing the Shelves DD4200 DD4500 and DD7200 cabling 57 ...
Страница 69: ...Figure 31 Cabling for HA DD9500 DD9800 systems in one rack Installing the Shelves DD9500 and DD9800 cabling 69 ...