3. Ensure the rack is grounded before connecting AC power from the main circuit.
4. To ensure redundant AC power, connect each power supply of the ES30 to a
different AC circuit. If the ES30 is to be connected to PDUs, then each power
supply of the ES30 must be fed from a different PDU, and each PDU must be
connected to a separate AC circuit.
5. Attach the power supplies on the rear panel of the Data Domain controller to
separate PDUs for redundant power distribution, one on each side of the rack.
6. The ES30 powers on immediately after you attach one of the power supplies on
the rear panel of the ES30 shelf to a PDU with power.
7. If multiple racks are used, complete the cabling of all shelves in all racks before
applying power.
Types of cabinets and power connections
The ES30 chassis is installed in two types of racks: 40U-C (existing racks) and the
40U-P (newer racks). The racks use one phase or 3 phase power connections.
This section describes the different types of racks and the power connections for the
ES30 chassis.
l
Single phase power connections for 40U-P (current racks)
on page 75
l
Single phase power connections for 40U-C (older racks)
on page 83
l
3-Phase power connections for 40U-P (current racks)
l
3-Phase power connections for 40U-C (older racks)
on page 106
Installing the Shelves
74
Data Domain ES30 Expansion Shelf and FS15 SSD Shelf
Hardware Guide
Содержание Data Domain ES30 Expansion Shelf
Страница 1: ...Dell EMC Data Domain ES30 Expansion Shelf and FS15 SSD Shelf Hardware Guide 302 002 104 REV 04 ...
Страница 8: ...Revision history 8 Data Domain ES30 Expansion Shelf and FS15 SSD Shelf Hardware Guide ...
Страница 16: ...Shelf Installation Overview 16 Data Domain ES30 Expansion Shelf and FS15 SSD Shelf Hardware Guide ...
Страница 37: ...Figure 10 Recommended cabling for DD990 integrated with Avamar Installing the Shelves DD990 cabling 37 ...
Страница 43: ...Figure 13 Recommended DD2500 cabling Installing the Shelves DD2500 cabling 43 ...
Страница 49: ...Figure 15 Recommended DD4200 cabling Installing the Shelves DD4200 DD4500 and DD7200 cabling 49 ...
Страница 53: ...Figure 19 Recommended DD4500 cabling Installing the Shelves DD4200 DD4500 and DD7200 cabling 53 ...
Страница 57: ...Figure 23 Recommended DD7200 cabling Installing the Shelves DD4200 DD4500 and DD7200 cabling 57 ...
Страница 69: ...Figure 31 Cabling for HA DD9500 DD9800 systems in one rack Installing the Shelves DD9500 and DD9800 cabling 69 ...