Limit: 

Max. ±120% of nominal output 

 
Output load: 

Burden if current output: Max. 10V (max. 1k

 

Burden if voltage output: Max. 20mA 

 
Output cable: 

Max. length 30m 

 
Ambient temperature:  -10…55

o

C (nominal) 

 

-25…70

o

C (operating) 

 

-40…70

o

C (storage) 

Temperature 
coefficient: 

Max. ±0.2% of full scale per 10°C 

 

 

Response time: 

Coupling 2W3/2var3, 3W3/3var3, 3W4/3var4 <225ms, 
typically 200ms 

 

Coupling 1W/1var, 1W4/1var4 <150ms, typically 125ms 

 

Coupling 1W3/1var3 <125ms, typically 100ms 

 
Ripple: 

Twice the class index (peak to peak measurement) according 
to IEC 688 

 
Galvanic separation: 

AC aux. supply models: 
Between inputs, outputs and aux. supply:  
3750V-50Hz-1 min. 

 

DC aux. supply models: 

 

Between inputs and outputs: 3750V-50Hz-1 min. 

 

Between inputs and supply: 3750V-50Hz-1 min. 

 

Between supply and outputs: 1500V-50Hz-1 min. 

 
Supply voltage: 

57.7-63.5-100-110-127-200-220-230-240-380-400-415-440-

 

450-480-660-690V AC ±20% 

 

24-48-110-220V DC -25/+30% 

 
Consumption: 

(Aux. supply) 3.5VA/2W 

 
Climate: 

HSE, to DIN 40040 

 
EMC: 

According to EN 61000-6-1/2/3/4 

 
Protection: 

Housing: IP40. Terminals: IP20, to IEC 529 and EN 60529 

 
Connections: 

Max. 2.5mm² multi–stranded 

 

Max. 4.0mm² single-stranded 

 
Materials: 

All plastic parts are self-extinguishing to UL94 (V1) 

 
Weight: 

0.650kg 

 
 

 

Содержание TAS-331DG

Страница 1: ...9615 Denmark E mail deif deif com DEIF A S Installation and start up instructions TAS 331DG Selectable AC transducer 4189300008G UK Watt or var transducer Supply and measuring voltage up to 690V Conf...

Страница 2: ...The un configured transducer is provided with a label with the following data Type designation DEIF s order ack no To be stated when contacting DEIF Coupling Measuring range Primary values Output ran...

Страница 3: ...mounting of it close to similar equipment possible however make sure there is min 50 mm between the top and bottom of the transducer and other equipment The DIN rail must always be placed horizontall...

Страница 4: ...and 3 The transducer is protected against ESD electrostatic electricity and further special protection against this during the mounting of the transducer is not necessary The below diagram illustrate...

Страница 5: ...L2 to term No 17 L3 to term No 19 L1 to term No 21 connected to L3 L3 to term No 17 L1 to term No 19 L2 to term No 21 Connection set up The transducer is equipped with a red LED for indication of wro...

Страница 6: ...eans of a screwdriver The front panel may be loosened in the right side first and is then totally demounted by moving the screw driver towards left Press with a screwdriver as indicated by the arrow a...

Страница 7: ...sly 2 x Un max for 10 s Load Min 480k Frequency range 30 45 65 80Hz Note For fundamental frequency 1 harmonic outside 20Hz 80Hz the input is fixed to 0 Indication Red LED function The LED is located b...

Страница 8: ...the class index peak to peak measurement according to IEC 688 Galvanic separation AC aux supply models Between inputs outputs and aux supply 3750V 50Hz 1 min DC aux supply models Between inputs and ou...

Отзывы: