Installation and start up instructions, TAS-331DG
4189300008G (UK)
Mounting instructions
TAS-331DG is designed for
panel
mounting,
being
mounted on a 35 mm DIN rail,
or by means of two 4-mm
screws.
Weight: Approx. 0.650 kg
The design of the transducer makes mounting of it close to similar equipment
possible, however make sure there is min. 50 mm between the top and bottom of the
transducer and other equipment.
The DIN rail must always be placed horizontally when several transducers are
mounted on the same rail.
Connection diagram
With voltages above 480V phase-phase.
The secondary side of the current transformer must be connected
to earth. Alternatively a double insulated current transformer can
be used.