Installation and start up instructions, TAS-331DG
4189300008G (UK)
Technical specifications
Accuracy:
Class 0.5 (-10…15…30…55°C) according to IEC 688
Influence, phase angle: ≤ ±0.75°
Meas. current (In)
0.75/1.5/3.0/6.0A
Meas. range: 0…200% I
n
I
n
can be set between 0.375…6A
Overload, currents:
20A max., continuously
75A max. for 10 s
240A max. for 1 s
Load:
Max. 0.5VA per phase
Meas. voltage (Un):
73/140/254/400V phase to neutral Meas. range: 30…120%U
n
U
n
can be set between 57…400V
127/240/440/690V phase to phase Meas. range: 30…120%U
n
U
n
can be set between 100…690V
Overload, voltages:
1.2 x U
n
max., continuously, 2 x U
n
max. for 10 s
Load:
Min. 480k
Frequency range:
30…45…65…80Hz
Note: For fundamental frequency (1. harmonic) outside 20Hz
…80Hz the input is fixed to 0
Indication:
Red LED function:
(The LED is located behind the front plate)
Incorrect wiring = constant light, only active for coupling 1W3,
2W3, 3W3(4) and 1var3, 2var3, 3var3(4). Check at power up,
in case of doubt disconnect supply and reconnect
Calibration error = flash frequency 5Hz
Configuration error = flash frequency 1Hz
Output:
1 analog output
Standard range:
Output (0...100%):
0...1mA, 0...5mA, 0...10mA, 0...20mA, 0...1V, 0...5V, 0...10V
Output (10...100%):
0.1...1mA, 0.5...5mA, 1...10mA, 2...20mA, 0.1...1V, 0.5...5V,
1...10V
Output (20...100%):
0.2...1mA, 1...5mA, 2...10mA, 4...20mA, 0.2...1V, 1...5V,
2...10V
Output (-100...0...100%):
-1...0...1mA, -5...0...5mA, -10...0...10mA, -20...0...20mA,
-1...0...1V, -5...0...5V, -10...0...10V
Other ranges possible