Register
address
Parameter
Scale Factor
Unit/
Interpretation
Bits/Sign
78
DG status
SGC mode
Config (1)
Run (0)
16/16
Mains healthy/unhealthy
--
True (1)
False (0)
15/16
DG operation mode
--
Scheduler-110
Cyclic-111
Auto-101
Manual-100
14-12/16
Load on Mains
True (1)
False (0)
11/16
Load on DG
--
True (1)
False (0)
10/16
Current DG status
--
Running
Stopped
9/16
DG stopped normally
--
True (1)
False (0)
8/16
DG stopped with fault
True (1)
False (0)
7/16
DG fail to start
--
True (1)
False (0)
6/16
Gen available
True (1)
False (0)
5/16
Common shut down
--
True (1)
False (0)
4/16
Common electric trip
--
True (1)
False (0)
3/16
Common warning
--
True (1)
False (0)
2/16
Common notification
--
True (1)
False (0)
1/16
79
Current time stamp
--
Min
Sec
Hexadecimal
80
Current time stamp
Week day
Hour
Hexadecimal
81
Current time stamp
Month
Day
Hexadecimal
82
Current time stamp
Year
Unsigned
Table 10.2
Example of Time stamp settings
Register address
Time
Hexadecimal
Decimal
79
Min
0x1215
Min = 0x12
18
Sec
Sec = 0x15
21
80
Week day
0x0414
Week day = 0x04
4
Hour
Hour = 0x0E
14
USER MANUAL 4189341226A UK
Page 54 of 72