Level 2
Range
Over-voltage Shutdown
(OVER VOLT SHUTDOWN)
Enable
Disable
Over-voltage Shutdown Threshold
(OV SHUTDOWN THRESH)
105 to 350 V phase-neutral
Over-voltage Warning
(OVER VOLT WARNING)
Enable
Disable
Over-voltage Warning Threshold
(OV WARNING THRESHOLD)
100 to 345 V phase-neutral
Table 6.16
Frequency Monitoring (FREQ MONITOR)
Level 2
Range
Under-frequency Shutdown
(UNDER FREQ SHUTDOWN)
Enable
Disable
Under-frequency Shutdown Threshold
(UF SHUTDOWN THRESH)
10.0 to 59.0 Hz
Under-frequency Warning Enable
(UNDER FREQ WARNING)
Enable
Disable
Under-frequency Warning Threshold
(UF WARNING THRESHOLD)
11.0 to 60.0 Hz
Over-frequency Shutdown Enable
(OVER FREQ SHUTDOWN)
Enable
Disable
Over-frequency Shutdown Threshold
(OF SHUTDOWN THRESH)
26.0 to 75.0 Hz
Over-frequency Warning Enable
(OVER FREQ WARNING)
Enable
Disable
Over-frequency Warning Threshold
(OF WARNING THRESHOLD)
25.0 to 74.0 Hz
Table 6.17
Current Monitoring (CURRENT MONITOR)
Level 2
Range
CT Ratio
(LOAD CT RATIO)
0 to 8000 / 5
Over-current Action
(OVER CURR ACTION)
None
Notification
Warning
Electrical Trip
Shutdown
Over-current Threshold
(OVER CURR THRESHOLD)
5 to 10000 A
Over-current Delay
(OVER CURR DELAY)
1 to 600 s
CT Correction Factor
0.900 to 1.100
CT Location
(CT LOCATION)
On Alt Output Cable
On Load Cable