Alarm status
Register
address
Parameter
Scale Factor
Unit/
Interpretation
Bits/Sign
65*
Alarm 1
Low oil pressure
--
--
13/16-16/16
High coolant temperature
--
--
9/16-12/16
Low fuel level
--
--
5/16-8/16
Water level switch
--
--
1/16-4/16
66*
Alarm 2
Underspeed
--
--
13/16-16/16
Overspeed
--
--
9/16-12/16
Fail to start
--
--
5/16-8/16
Fail to stop
--
--
1/16-4/16
67*
Alarm 3
Reserved
--
--
13/16-16/16
Reserved
--
--
9/16-12/16
Generator low frequency
--
--
5/16-8/16
Generator high frequency
--
--
1/16-4/16
68*
Alarm 4
Generator high current
--
--
13/16-16/16
Generator overload
--
--
9/16-12/16
Unbalanced load
--
--
5/16-8/16
Emergency stop
--
--
1/16-4/16
69*
Alarm 5
Charge alternator failure
--
--
13/16-16/16
Maintenance
--
--
9/16-12/16
Reserved
--
--
5/16-8/16
Reserved
--
--
1/16-4/16
70*
Alarm 6
Battery low voltage
--
--
13/16-16/16
Battery high voltage
--
--
9/16-12/16
Temperature circuit open
--
--
5/16-8/16
Reserved
--
--
1/16-4/16
71
Alarm 7
Fuel theft
--
--
13/16-16/16
Magnetic pick up fault
--
--
9/16-12/16
Oil pressure open circuit
--
--
5/16-8/16
Auxiliary input I
--
--
1/16-4/16