No.
Alarms
Causes/Indication
Actions
4
Low Fuel level (Sensor)
Indicates that the amount of fuel level is below the preset
threshold. This condition is detected only when engine is
on.
Shutdown
Warning
Low Fuel level (Switch)
Indicates that the amount of fuel level measured is low
through switch.
Shutdown
Warning
Electrical Trip
Notification
5
Low Water Level (Switch)
Indicates that radiator water level is below the preset
threshold.
Shutdown
Warning
Electrical Trip
Notification
6
Auxiliary input/User defined
name
Configured auxiliary input has triggered longer than preset
duration.
Shutdown
Warning
Electrical Trip
Notification
7
Anlg LOP Ckt Open
The oil pressure sensor is not detected (circuit open).
Shutdown
Warning
Electrical Trip
Notification
8
Engine Temp Ckt Open
The temperature sensor is not detected (circuit open).
Shutdown
Warning
Electrical Trip
Notification
9
Fuel Level Ckt Open
The fuel level sensor is not detected (circuit open).
Shutdown
Warning
Electrical Trip
Notification
10
Fuel Theft
The fuel consumption has exceeded the preset threshold.
Warning
11
Emergency Stop
Configured as digital input has triggered longer than preset
or when an immediate shutdown is required.
Shutdown
12
Fail To Stop
It is detected that genset is still running after sending stop
command.
Shutdown
13
Fail To Start
Indicates that genset has not started after the preset
number of start attempts.
Shutdown
14
L1 Phase Over Voltage
Indicates that genset (L1) phase voltage has exceeded the
preset over-voltage threshold.
Shutdown
Warning
15
L2 Phase Over Voltage
Indicates that genset (L2) phase voltage has exceeded the
preset over-voltage threshold.
Shutdown
Warning
16
L3 Phase Over Voltage
Indicates that genset (L3) phase voltage has exceeded the
preset over-voltage threshold.
Shutdown
Warning
17
L1 Phase Under Voltage
Indicates that genset (L1) phase voltage has fallen below
preset under-voltage threshold.
Shutdown
Warning
18
L2 Phase Under Voltage
Indicates that genset (L2) phase voltage has fallen below
preset under-voltage threshold.
Shutdown
Warning
19
L3 Phase Under Voltage
Indicates that genset (L3) phase voltage has fallen below
preset under-voltage threshold.
Shutdown
Warning
20
DG Phase Reversal
Alternator phase sequence (L1-L2-L3) is not correct.
Shutdown
Warning
Electrical Trip
Notification
USER MANUAL 4189341226A UK
Page 45 of 72