3.3.3 Checking the Ethernet connections
You can use the LEDs on the front plate of PCM3.1 to check the network status of the five Ethernet connections:
Symbol
Expected
Unexpected state and action
, 1 to 5
Green, or
Green
(flashing)
Off
• Have you used an Ethernet port on PCM3.1?
◦ The communication will NOT work if you use one of the
internal communication ports
on PSM3.1
.
• Is the power on for the connected equipment?
• Check the Ethernet cable bend radius.
• Plug into another Ethernet port.
• Use another Ethernet cable.
• If a switch is used, check the switch configuration.
• Replace the PCM3.1.
3.4 Checking display unit
3.4.1 Display unit
Check that the display unit is powered on, and that there is communication with the controller.
3.5 Controller software update
3.5.1 Connecting to a controller with PICUS
To connect to a controller:
1. Connect an Ethernet cable to any Ethernet port on your computer.
2. Connect the other end of the Ethernet cable to port 3 on the controller's processor and communication module (PCM).
This hardware module is in slot 7 of the controller rack.
• Port 3 is the recommended port. You could use any PCM Ethernet port.
• DO NOT use the internal communication ports on the power supply module (PSM) in slot 1.
3. Launch PICUS from your local computer.
• PICUS automatically locates the controller(s) connected to the network.
4. Select the controller on the
Connect
screen.
5. Select a
user
and enter a
password
.
• If the
user
and
password
are correct, you are logged on to the controller.
See
PICUS
,
Default permissions
in the
Designer's handbook
for factory default user names and passwords.