Description
Notes
Update mode on all
The running mode for all controllers in the power management system is updated
to the selected mode.
Store common settings
See
Handling settings for sections
in
Option G5 Power management
.
Open MB
Open the mains breaker.
Close MB
Close the mains breaker.
Auto start/stop
ON = Start, OFF = Stop.
Autoswitch off
Auto-switch is not enabled.
Autoswitch static
Auto-switch enabled for static section.
Autoswitch dynamic
Auto-switch enabled for dynamic section.
Autoswitch all
Auto-switch enabled for all sections.
Activate MB parallel
Mains breaker in parallel is activated (parameter 8182).
Deactivate MB parallel
Mains breaker in parallel is deactivated (parameter 8182).
Activate no break transfer
No break transfer is activated.
Deactivate no break transfer
No break transfer is deactivated.
Activate MB close failure start
MB close failure start is activated.
Deactivate MB close failure start
MB close failure start is deactivated.
Select three phase system
Sets the controller to work in a three-phase system.
Select split L1L3 phase system
Sets the controller to work in a two-phase system (L1-L3).
Select split L1L2 phase system
Sets the controller to work in a two-phase system (L1-L3).
Select single phase system
Sets the controller to work in a single-phase system (L1).
Inductive reference
Inductive cos phi reference.
Capacitive reference
Capacitive cos phi reference.
Act. power offset [1-3]
Activate the selected power reference offset.
Deact. power offset [1-3]
Deactivate the selected power reference offset.
Act. cos phi offset [1-3]
Activate the cos phi reference offset.
Deact. cos phi offset [1-3]
Deactivate the cos phi reference offset.
MB close inhibit
Prevents the mains breaker from closing.
Reset horn
Reset the horn relay.
Reset I max. demand
Reset the peak current detected in the controller.
Reset I thermal demand
Reset the thermal current detected in the controller.
Pulse counter [1-2]
Increase the selected pulse counter.
Reset pulse counter [1-2]
Reset the selected pulse counter.
Set parameter [1-2]
Select the parameter set for busbar nominal settings.
Set BB U
NOM
= Mains U
NOM
Busbar nominal voltage is considered equal to the mains nominal voltage.
Mains sync. inhibit activate
Activates the close inhibit functionality on the mains breaker.
Mains sync. inhibit deactivate
Deactivates the close inhibit functionality on the mains breaker.
Ack. mains protection alarms
Acknowledges all mains alarms including: 1270-1430, 1660, 1700, 1960, 1970,
7480-7490.
Mains Okay
This function can be used if an input has been configured to
Mains Okay
. When it
is set, the command Mains Okay is given. This command is sometimes called
External Mains Okay
.
Application note 4189341276B EN
Page 42 of 50