Description
Notes
Select application [1-4]
Power management: Select the application from the controller.
Open BTB
Open the bus tie breaker.
Close BTB
Close the bus tie breaker.
Select three phase system
Sets the controller to work in a three-phase system.
Select split L1L3 phase system
Sets the controller to work in a two-phase system (L1-L3).
Select split L1L2 phase system
Sets the controller to work in a two-phase system (L1-L3).
Select single phase system
Sets the controller to work in a single-phase system (L1).
Reset horn
Reset the horn relay.
Reset I max. demand
Reset the peak current detected in the controller.
Reset I thermal demand
Reset the thermal current detected in the controller.
Pulse counter [1-2]
Increase the selected pulse counter.
Reset pulse counter [1-2]
Reset the selected pulse counter.
Set parameter [1-2]
Select the parameter set for nominal settings.
Ack. BB protection alarms
Acknowledges all busbar alarms including: 1270-1430, 1660, 1700, 1960, 1970,
7480-7490.
Access lock
Activates access lock.
Direct close on dead BA and dead BB
See
Special M-Logic function - BTB direct close
in
Option G5 Power
management
.
Direct close breaker on dead BA or dead BB
See
Special M-Logic function - BTB direct close
in
Option G5 Power
management
.
Breaker configuration: Normal Close
See
Tie breaker configuration
in
Option G5 Power management
.
Breaker configuration: Normal Open
See
Tie breaker configuration
in
Option G5 Power management
.
Assume all BTB POS fdb OFF in case of pos
fail or ID missing
Fault handling procedure.
More information
See
Option G5 Power management
for information about BTB commands.
5.1.4
Group tie breaker controller commands
Commands for group tie breaker
Description
Notes
Island
Island function mode.
AMF
AMF (Automatic Mains Failure) function mode.
Peak shaving
Peak shaving function mode.
Fixed power
Fixed power function mode.
Mains power export
Mains power export function mode.
Load take over
Load take over function mode.
Genset group
Semi-Auto mode
Semi-auto running mode.
Test mode
Test running mode.
Auto mode
Auto running mode.
Application note 4189341276B EN