7.9.4.

 

ERROR CODES 

Code 

Symptom 

Possible causes 

F02 
Contact service centre 

 

5-second audible signal from the receiver 

 

Flame  does  not  respond  to  remote  control,  no 
ignition. 

 

No contact of microswitch with a cam on drive knob. 

 

Incorrect connections of drive cables. 

 

Reversed polarity or fault of the microswitch. 

 

Bent knob of the motor. 

F03 
Contact service centre 

 

5-second audible signal from the receiver 

 

Firing up interrupted. 

 

Flame does not respond to remote control, no 
ignition. 

 

Incorrect connections of thermocouple cables. 

 

The thermocouple is not connected to the controller. 

 

ON/OFF switch in ”O” (OFF) position. 

F04 
Disturbed firing up sequence. Wait a 
minute and retry. 

 

No ignition flame for 30 seconds. 

 

No supply gas. 

 

Air in the supply pipe of the ignition burner. 

 

No spark. 

 

Reversed polarity in thermocouple cables. 

 

Check if the opening of ignition burner corresponds to 
the type of supply gas. 

F05 
Contact service centre 

 

Failed ignition of ignition burner or its shutdown. 

 

Drive (knobs of primary valve) remains in operating 
position of the ignition burner 

 

Too low voltage from thermocouple 

 

Presence of air in the supply pipe of the ignition burner. 

 

Too low pressure on inlet. 

 

Damaged or incorrect thermocouple 

F06

 

Contact service centre 

 

Three (3) failed firing up attempts within 5 minutes 

 

The flame does not respond to the settings, no flame 
in the ignition burner. 

 

No supply gas. 

 

Presence of air in the supply pipe of the ignition burner. 

 

No spark. 

 

Reversed polarity of thermocouple cables. 

 

Check if the opening of ignition burner corresponds to 
the type of gas. 

F07 
Replace batteries in the remote control 

 

Flashing battery icon on the remote control screen. 

 

Low voltage of batteries in the remote control. 

F08 
Contact service centre 

 

Low voltage of batteries supplying the receiver. 

 

Short audible signals within three (3) seconds during 
operation of the valve drive. 

 

Too low voltage of batteries in the receiver. 

F10 
Contact service centre 

 

Failed ignition of the primary burner and shutdown of 
ignition burner. 

 

Ignition locked for two minutes 

 

Second thermocouple in incorrect position 

 

Incorrect  connection  of  cables  of  the  second 
thermocouple.  

 

Decorative items installed incorrectly. 

 

Clogged openings of the primary burner. 

F12

 

Contact service centre 

 

Valve drive in ignition burner position. 

 

Temperature of battery-operated receiver exceeded 60 
°C. 

 

Check air circulation and temperature of housing. 

F13 
Contact service centre 

 

Valve drive in ignition burner position. 

 

Fan operates on level 4 for 10 minutes (temperature 
over 80 °C) 

 

Temperature of receiver exceeded 80 °C. 

 

Check air circulation and temperature of housing. 

F14 
Contact service centre 

 

Audible signal from receiver lasting 5 seconds. 

 

Flame  does  not  respond  to  change  of  settings,  no 
ignition. 

 

Receiver  software  does  not  support  a  second 
thermocouple. 

 

Incorrect or damaged receiver. 

F15 
Contact service centre 

 

Audible signal from receiver lasting 5 seconds. 

 

Flame  does  not  respond  to  change  of  settings,  no 
ignition. 

 

Incorrectly connected second thermocouple. 

 

The second thermocouple not connected. 

F16 
Remote control outside the range 

 

No  temperature  indication  on  the  remote  control 
screen or in the app. 

 

Remote control located too far away from the receiver 
for more than 1.5 h. 

 

Interface error. 

F17 
Contact service centre 

 

Flame does not respond to changes, no ignition. 

 

Input voltage exceeds 7.25 V. 

 

DC rectifier failure. 

F18 
Contact service centre 

 

Wall-mounted control panel does not work. 

 

Panel locked 

 

Short-circuit in cable or button. 

F19 
Contact service centre 

 

The ignition burner goes out when the primary valve 
is opened. 

 

Too low voltages from thermocouple. 

 

Thermocouple failure 

 

Too low gas pressure on inlet. 

 

Too high distance of thermocouple from a flame 

 

Accumulation of carbon on thermocouple. 

 

Control failure 

 

Additional resistance in thermocouple circuit. 

F26 
Contact service centre 

 

Impossible increase in flame height after ignition. 

 

Fan operates on level 4 for 10 minutes (T > 80 °C) 

 

Battery-operated receiver reached temperature over 60 
°C 

 

Network-supplied  receiver  reached  temperature  over 
80 °C. 

F27 
Contact service centre 

 

Flame does not respond to change of settings. 

 

No flame control from controller level. 

 

 

No connection of receiver with WiFi network or remote 
control. 

Содержание VITAL 37S

Страница 1: ...erating manual gas fired convection room heater DEFRO HOME VITAL 37 S 51 S BP BL U C T gas type G2 350 G20 G27 G31 G30 translation of original operating manual edition 1 b May 2021 destination countri...

Страница 2: ...deklaracja musi by przekazana wraz z urz dzeniem w przypadku odst pienia w asno ci innej osobie This Declaration of Conformity becomes invalid if any changes have been made to the device if its constr...

Страница 3: ...illed copy of the Warranty Card to the following address DEFRO Sp z o o Sp k Centrum Serwisowe Ruda Strawczy ska 103a 26 067 Strawczyn serwis defro pl By sending back your Warranty Card you will be re...

Страница 4: ...2 Preparation 16 7 3 Information 16 7 4 Deactivation of remote control function 16 7 5 Activation of remote control function 16 7 6 Control of FIREPLACE with a remote control 16 7 6 1 Setting temperat...

Страница 5: ...34 13 PRODUCT WARRANTY TERMS AND CONDITIONS 35 13 1 Warranty conditions 48h Service 36 14 WARRANTY CARD 37 15 CARRIED OUT WARRANTY REPAIRS AND MAINTENANCE 38 16 WARRANTY CARD copy to send back 39 17...

Страница 6: ...m the action of high temperature Non compliance with the recommendations distinguished in this way may cause a fire or burns Hint Informative symbol Useful information and hints are marked in this way...

Страница 7: ...The body of the heater is made of steel sheet with combustion chamber located inside and lined with additional panels made of sheet rear and sides Picture 1 Design of DEFRO HOME VITAL heater 1 explos...

Страница 8: ...pply V DC 6 Weight1 kg 90 90 90 90 90 1 Device weight depends on selected design version and its equipment 2 Level for C11 equipment acc to PN EN 613 2002 A1 2004 Table 2 Technical data of GV60 regula...

Страница 9: ...O HOME VITAL 51 S U Picture 8 Dimensions of DEFRO HOME VITAL 51 S T Picture 9 Dimensions of DEFRO HOME VITAL 51 S 983 47 808 330 297 150 883 370 115 98 111 783 188 350 828 309 781 370 107 98 154 720 4...

Страница 10: ...ts pressure and whether the current settings of a heater are correct VITAL heater should be supplied with the same type of gas as the other gas fired equipment if any in the home of their installation...

Страница 11: ...reduction of total allowable length of the pipe by 1 meter First elbow connected to the equipment is not taken into consideration Vertically lead pipes should be fixed to the wall using brackets arra...

Страница 12: ...f the existing chimney in connection with a terminal should be protected against flooding or clogging and the terminal should be installed in a way ensuring its correct operation Penetration of concen...

Страница 13: ...y burner by turning the screw clockwise rotation increases the pressure When the adjustment has beencompletedyoushouldprotect the following fixtures with blanking plugs pressure control screw and afte...

Страница 14: ...tion of concentric coaxial system acc to allowed configuration for ducts leading set the flue gas flow damper in half of opening position Close the window panel and set maximum load of the heater Meas...

Страница 15: ...of contact with wooden wall or wall made of other inflammable material it is appropriate to insulate flue gas discharge pipe In case of floor made of inflammable materials it is appropriate to prepar...

Страница 16: ...control knob to ON Make sure that four 4 AA batteries have been correctly installed in the receiver Remote control operating at the 868 MHz band also requires preparation You should enter the transmi...

Страница 17: ...tton firing with one button on remote control or two button and at the same time firingup with two buttons until twoshort audible signals will be heard and an icon confirming the ignition will be flas...

Страница 18: ...what temperature should be maintained Eco mode controls the fireplace so as to maintain the set temperature but inthemore economical way Thecontroller forces maximum height of the flame if thetempera...

Страница 19: ...ed once again for a while and minutes field will be flashing Select minutes using buttons Confirm the setting once again with the button The system will go to configuration of switch off time Switch o...

Страница 20: ...in manual control mode All operations are then performed directly from the GV60 valve level located inside the cabinet Control components used during manual control are presented on the picture 24 To...

Страница 21: ...ion locked for two minutes Second thermocouple in incorrect position Incorrect connection of cables of the second thermocouple Decorative items installed incorrectly Clogged openings of the primary bu...

Страница 22: ...ange of settings No flame control from controller level No WiFi connection with WiFi module of the controller Switched off WiFi connection on the control device F42 Check WiFi Flame does not respond t...

Страница 23: ...omponents should not touch the window panel Components should not cover the flame of the control burner It is forbidden to cover outlet holes of the primary burner and gaps in the floor of the combust...

Страница 24: ...installation of chunks 2 Lay item no 1 as presented on both photos The component should remain stable at the centre of the ignition burner and parallel to the rear wall The wider end of thechunk shoul...

Страница 25: ...th photos Chunk should be stable due to incisions adapted to the burner The distance between the holes in the burner and the edge of the chunk should be approx 5 mm right corner of the burner the edge...

Страница 26: ...c to the incision and photos Similarly as for chunk no 2 the distance between the holes in the burner and the edge of the chunk should be approx 5 mm left corner of the burner the edge of the ceramic...

Страница 27: ...27 5 Lay chunk no 4 as presented on the photos The chunk should not cover burner openings and should be supported in half way on chunk no 1 gas holes...

Страница 28: ...28 gas holes left corner of the burner...

Страница 29: ...29 6 Lay item no 5 as presented on photos The chunk should be stable and should not cover gas openings in the floor right corner of the burner gas gaps...

Страница 30: ...30 7 Set the chunk no 6 as the last one it should be laid on chunk no 5 and be supported on chunk no 4 and right corner of the burner...

Страница 31: ...31 right corner of the burner...

Страница 32: ...32 8 3 LAYING OF DECORATION IMITATING THE STONES Items made of stone should be laid on the floor of the combustion chamber so as to avoid covering of gas openings...

Страница 33: ...or this purpose they should not be used on other surfaces or components e g painted because they may damage them 9 2 WINDOW PANEL DISMANTLING To clean the window panel combustion chamber or install de...

Страница 34: ...arbon monoxide is a result of defect or leaks in the system Given the impossibility to detect presence of this hazardous gas you should Perform inspections of the system and its maintenance by authori...

Страница 35: ...pr assembly of window panels iv decorative items supplied with the equipment or purchased by the customer v all damages resulting from incorrect transport from distributor to the customer incorrect i...

Страница 36: ...accept the claim and to charge its costs to buyer 25 Provisions of this document shall not limit in any way the rights resulting from the claim filed based on the statutory guarantee The warranty doe...

Страница 37: ...s been delivered as complete the device showed no failure during the first start up carried out by a service company has received the Operating Manual and equipment s installation manual with this War...

Страница 38: ...38 15 CARRIED OUT WARRANTY REPAIRS AND MAINTENANCE No date fault description repaired element description of repairs comments Stamp and signature of Service 1 2 3 4 5 6 7 8 9 10...

Страница 39: ...s been delivered as complete the device showed no failure during the first start up carried out by a service company has received the Operating Manual and equipment s installation manual with this War...

Страница 40: ...40...

Страница 41: ...technician Way of fault removal Advice DESCRIPTION END OF COMPLAINT Name and surname of service technician Fault removal date Justness of complaint Duration of repair Fault defect has been removed th...

Страница 42: ......

Страница 43: ...hnician Way of fault removal Advice DESCRIPTION END OF COMPLAINT Name and surname of service technician Fault removal date Justness of complaint Duration of repair Fault defect has been removed the eq...

Страница 44: ......

Страница 45: ...technician Way of fault removal Advice DESCRIPTION END OF COMPLAINT Name and surname of service technician Fault removal date Justness of complaint Duration of repair Fault defect has been removed th...

Страница 46: ......

Страница 47: ...47 20 REGISTER OF INSPECTIONS OF SMOKE DUCTS date stamp and signature of chimneysweep date stamp and signature of chimneysweep...

Страница 48: ...mbol Unit value Heat output Rated heat output Pnom kW 6 0 Minimum heat output Pmin kW 3 6 Performance Performance at rated thermal power th nom Performance at minimal thermal power indicative th min A...

Страница 49: ...ol Unit Value Heat output Rated heat output Pnom kW 5 5 Minimum heat output Pmin kW 3 3 Performance Performance at rated thermal power th nom Performance at minimal thermal power indicative th min Aux...

Страница 50: ......

Страница 51: ...51...

Страница 52: ...509 702 720 509 577 900 DEFRO Sp ka z ograniczon odpowiedzialno ci Sp ka komandytowa 00 403 Warszawa ul Solec 24 253 Production plant Ruda Strawczy ska 103 A 26 067 Strawczyn tel 41 303 80 85 biuro d...

Отзывы: