DSE Model 5520 Automatic Mains Failure Control and Instrumentation System Operators Manual
5520 OPERATING MANUAL ISSUE 1 04/02/05 AM
24
DESCRIPTION OF CONTROLS
The following section details the function and meaning of the various controls on the module.
3.5 TYPICAL LCD DISPLAY SCREENS
3.5.1 TYPICAL STATUS DISPLAY
Status
Waiting in Auto
Mains on load
Indicates that the module is in Automatic and that the mains is on
load (closed). The unit will respond to either a mains failure or an
active remote start.
Starting in auto 10s
Mains on load
Cranking attempt 1
Indicates that the module is in automatic and that a start sequence
has been initiated, either by a mains failure or remote start input.
The module is attempting to crank the generator.