DSE Model 5520 Automatic Mains Failure Control and Instrumentation System Operators Manual
5520 OPERATING MANUAL ISSUE 1 04/02/05 AM
31
3.9.3 LIST OF ADJUSTABLE PARAMETERS
(Factory default settings are shown in bold italicised text)
Section
Parameter as shown on display
Values
Input settings
Oil Pressure Pre Alarm
0 bar -4bar (
1.17bar
)
Oil Pressure Shutdown
0 bar -4bar (
1.03bar
)
High Coolant Temp Pre Alarm
80
C -140
C (
115
C
)
High Coolant Temp Shutdown
80
C -140
C (
120
C
)
Low Coolant Temp Alarm
67
C -137
C (
disabled
)
Low Fuel Level Alarm
0%-100% (
disabled
)
Timers
Mains Transient Delay
0-10s (
2s
)
Gen Transient Delay
0 -10s (
0s
)
Start Delay
0 -60m (
5s
)
Pre Heat Time
0 -60m (
0s
)
Crank Time
0 -60s (
10s
)
Crank Rest Time
0-60s (
10s
)
Safety On Delay
0-30s (
10s
)
Overspeed Overshoot Delay
0-10s (
0s
)
Warm Up Time
0-60m (
0s
)
Transfer Delay
0-10s (
0.75s
)
Return Delay
0 -60m (
30s
)
Cooling Run Time
0-60m (
30s
)
Fail To Stop Delay
0-30s (
30s
)
Low Battery Delay
0-10m (
1m
)
High Battery Delay
0-10m (
1m
)
Gen Reverse Power Delay
0-30s (
2s
)
Mains
Mains Under Voltage Alarm
50V-360V ph-N (
184V
)
Mains Over Voltage Alarm
50V-360V ph-N (
277V
)
Mains Under Frequency Alarm
0Hz -75Hz (
45Hz
)
Mains Over Frequency Alarm
0Hz -75Hz (
55Hz
)
Generator
Generator Under Voltage Shutdown
50V-360V ph-N (
184V
)
Generator Under Voltage Pre Alarm
50V-360V ph-N (
196V
)
Generator Nominal Voltage
52V-330V(
230V
)
Generator Over Voltage Pre Alarm
50V-360V ph-N (
265V
)
Generator Over Voltage Shutdown
50V-360V ph-N (
277V
)
Generator Under Frequency Shutdown
0Hz -75Hz (
40Hz
)
Generator Under Frequency Pre Alarm
0Hz -75Hz (
42Hz
)
Generator Nominal Frequency
0Hz
–
74Hz
(
50Hz
)
Generator Over Frequency Pre Alarm
0 -75Hz (
55Hz
)
Generator Over Frequency Shutdown
0 -75Hz (
57Hz
)
Generator Over Current Trip
100-200% full load rating (
100%
)
Generator Short Circuit Trip
50%-300% full load rating (
200%
)
Generator Reverse Power Trip
0%-200% full load rating (
35kW
)
Earth Fault Trip
1%-100% full load rating (
10%
)
Engine
Overspeed Overshoot
0-10 (
0%
)
Plant Battery Under Volt Alarm
0-24V (
10V
)
Plant Battery Over Volt Alarm
0-24V (
30V
)
Charge Alternator Failure Alarm
0-24V (6
V
)
Engine Underspeed Shutdown
0-6000RPM (
disabled
)
Engine Underspeed Pre Alarm
0-6000RPM (
disabled
)
Engine Overspeed Pre Alarm
0-6000RPM (
disabled
)
Engine Overspeed Shutdown
0-6000RPM (
disabled
)
Display
Language
ENGLISH
, OTHERS
(see note below)
Contrast
|
Clock
Date and Time
dd mmm yyyy hh:mm
Misc
Auto Scroll Time
0-10s (
2.0s
)