DSE Model 5520 Automatic Mains Failure Control and Instrumentation System Operators Manual
5520 OPERATING MANUAL ISSUE 1 04/02/05 AM
48
5.4.3 JOHN DEERE
PLUG
“A”
8
WAY
55xx
PIN
No
55xx
DESCRIPTION
John Deere 21-pin Deutsch
connector
NOTES
4
Fuel relay
output
G, J
G = Switched ECU power, J =
Ignition
5
Start relay
output
D
Start
PLUG
“C”
9
WAY
55xx
PIN
No
55xx
DESCRIPTION
John Deere 21-pin Deutsch
connector
NOTES
23
CANbus
common
-
Screen for the J1939 cable.
Connect at 55xx end only.
24
CANbus H
V
J1939 + Use only screened 120
impedance cable approved
specifically for use in CANbus
applications.
25
CANbus L
U
J1939 - Use only screened 120
impedance cable approved
specifically for use in CANbus
applications.