4.3.1
Linear network
Linear network with a maximum of four sanitary extractor fan
outlets
In this configuration, the air duct vacuum pressure set point (parameter
) must be set to 1 (= 100 Pa).
1 Sanitary extractor fan outlets, Ø 80 mm (bathroom/WC)
2 Kitchen extractor fan outlet, Ø 125 mm
3 Thermodynamic water heater
4 Roof-mounted discharge
5 Duct (insulated if outside of the heated area)
6 125/80 Tee fitting
7 160 Tee f 160/125 reduction sleeve
Important
This configuration may include a maximum of:
2 bathrooms
2 WCs
1 kitchen
Linear network with a maximum of 6 sanitary extractor fan
outlets
In this configuration, the air duct vacuum pressure set point (parameter
) must be set to 1 (= 100 Pa).
1 Sanitary extractor fan outlets, Ø 80 mm (bathroom/WC)
2 Kitchen extractor fan outlet, Ø 125 mm
3 Thermodynamic water heater
4 Roof-mounted discharge
5 Duct (insulated if outside of the heated area)
6 160/80 Tee f 160/80 reduction sleeve
7 160/80 reduction sleeve
Fig.2
M002827-E
1
7
5
2
Ø125
Ø125
Ø160
Ø125
Ø80
Ø80
Ø80
Ø80
4
5
6
3
Fig.3
C004747-A
1
5
7
2
Ø125
Ø160
Ø160
Ø160
Ø80
4
5
3
6
4 Description of the product
EN-7602142 - v11 - 24042019
TWH 200 EV
17