6. To return to the main display, press the MENU key.
Tab.11
Counter
Description
Unit
1
Estimated electrical energy consumption
kWh
2
Electrical energy consumed by the compressor over the last 24 hours
The counter is reset to zero every day at 00:00
Wh
3
Electrical energy consumed by the electrical back-up over the last 24 hours
The counter is reset to zero every day at 00:00
Wh
4
Number of hours powered on
h
5
Instantaneous output
This value is only available if the control module is connected using a wire
W
Resetting the counters to zero
1. Press the MENU key once.
The SEtP 1 menu is displayed.
2. Press the key 4 times.
The Co un 5 menu is displayed.
3. Press the MODE key to go into the Counters menu.
The number for the counter is shown on the right-hand side of the
screen.
4. Use the and keys to display Coun rSt.
5. Press the reset key to reset all the counters to zero.
6. Confirm with the MODE key.
7. To return to the main display, press the MENU key.
6.7
Modifying the installer parameters
Caution
Modification of the factory settings may adversely affect the
operation of the appliance.
6.7.1
Accessing the parameters
To prevent handling errors, access to this menu requires the use of the
access code 012.
The parameters
to
must only be edited by a qualified
professional.
1. Press the MENU key once.
The SEtP 1 menu is displayed.
Fig.43
C004786-A
1
4
3
4
1
2
MENU
MODE
Fig.44
C003210-C
1
1
4
3
4
1
2
MENU
MODE
6 Commissioning
EN-7602142 - v11 - 24042019
TWH 200 EV
51