Tab.13
Network type
Value for parameter
Linear network
= 1 (= 100 Pa)
Linear network with the Ø 80 option
= 1 (= 100 Pa)
Multi-duct network
= 2 (= 125 Pa)
Warning
If this parameter is not set correctly, the installation will not
comply with the technical specifications.
We cannot be held liable for any damage or disruption caused
by a failure to respect these instructions.
For more information, see
Operating principle, page 16
6.7.4
Control system sequence
Tab.14 Control system sequence
Status
Sub-status
Operating
0
0
Standby
5
Post-operation of the compressor
8
Management of the fan
1
1
Anti-short cycle
5
Post-operation of the compressor
8
Management of the fan
4
1
Anti-short cycle
2
Domestic hot water production with the compressor
3
Domestic hot water production with back-up
4
Domestic hot water production with the compressor and back-
up
5
Post-operation of the compressor
9
–
Lockout present
6.7.5
Restoring the factory settings
1. Simultaneously press the and keys for 5 seconds.
The rSt menu is displayed.
Fig.47
C003495-C
3
1
4
3
4
1
2
MENU
MODE
6 Commissioning