5 ELECTRICAL CONNECTIONS
Execute the wiring following the directions of “Table 1” and diagrams on page 26.
WARNING
For adequate electrical safety, keep low safety voltage wires (controls, electro-locks, antenna, auxiliary power) clearly separate
from 230V ~ power wires
(minimum 4 mm in air or 1 mm via supplementary insulation)
placing them in plastic raceways and securing
them with adequate clamps
near terminal boards.
WARNING
For connection to the mains, use a multipolar cable having a minimum section 3x1,5 mm² and complying with the current
regulations. For connecting the motors, use a minimum cross section 1,5 mm² cable and complying with the current regulations. As
an example, if the cable is out side (outdoor), must be at least equal to H05RN-F, whereas if it (in a raceway), must be at least equal to
H05VV-F.
WARNING
All wires must be striped and unsheathed
in the immediate vicinity of terminals
. Keep wires slightly longer to subsequently
eliminate any excess.
WARNING
To connect the encoder to the control panel, use only a dedicated cable 3x0,22mm
2
.
Table 1 “terminal board connections”
1
Unused
2-3-4
Motor 1 encoder output
5-6
Motor 1 output max 5A
7-8
7 (+)
24 V
Flashing light output max 5W
8 (-)
9-13
9 - N.C.
Input 4 FCC 1. If it intervenes it stops M1 closing.
If unused, short circuit
.
If
the
installation
req
uires
dif
feren
t
commands
and
/ or
additional
to
the
stan
dar
d,
you
can
configure
each in
put t
o the req
uired rat
e.
R
ef
er t
o Chap
ter
“
Adv
anced Programming”.
13 - Com
10-13
10 - N.C.
Input 3 FCA 1. If it intervenes it stops M1 opening.
If unused, short circuit
.
13 - Com
11-13
11 - N.C.
Input 2 PHOTO 1. When enabled (see parameter P050 in the table), activation of
PHOTO 1 provokes: an inversion of direction (during closing), the arrest of the move-
ment (during opening), prevent the start (gate closed).
If unused, short circuit
.
13 - Com
12-13
12 - N.O.
Input 1 START. In case of intervention it provokes: the operator opening or closing. It
may operate as “inversion” mode (P049=0) or “step by step” mode (P049=1).
13 - Com
14-15
14 (-)
Stabilized 24 V
auxiliary power supply output
max 200mA
15 (+)
16-17
16 (+)
24 V
max 5W output for open gate fix warning light (if P052=0), flashing (if P052=1) or courtesy light
(if P052>1)
17 (-)
18
Aerial signal input
19
Ground aerial input
CON 1
Connection of motors metallic parts
CON 2
22 V ~ transformer power supply input
CON 3
Input for MEMONET connector
Содержание LIVI 3/24
Страница 2: ......
Страница 22: ...20 ...
Страница 42: ...40 ...
Страница 62: ...60 ...
Страница 82: ...80 ...
Страница 102: ...100 ...
Страница 122: ...120 ...
Страница 142: ...140 ...
Страница 162: ...160 ...
Страница 164: ...162 240 320 188 82 70 200 450 350 125 70 27 5 23 5 288 62 5 58 Ø35 50 235 50 38 min 48 max ...
Страница 166: ...164 1 2 m m ...
Страница 181: ......
Страница 182: ......
Страница 183: ......