17
1 –
Relay/open-collector outputs
The Cortex-360 can control its physical relays, or the transistors acting as relay drivers (open-collector mode).
By default, the eight relay jumpers are set for direct relay operation (RLY position). If you need open-collectors,
change the jumpers of the desired relays to OC Mode.
2 –
Status input
The status inputs can all be individually set for separate grounds or for internal grounds with pull-up resistors. DIP
Switches S11 and S12 select isolated grounds mode (Default is NO on all 16 inputs). DIP switches S9 and S10
select pull-up resistor mode (it is IN by default on all 16 inputs).
3 –
Metering input
The Cortex-360 metering inputs can be configured for 4-20 mA operation. To select this mode, place the jumper for
the desired metering input in the ON position. By default, the metering input jumpers are set for voltage
measurement (OFF position).
4 –
IOIOI
This serial port can be configured for RS-232, RS-422 or RS-485 operation. By default, the jumpers are set for RS-
232 operation.