DAT 6000
18
PRELIMINARY
Data Format
The module acquires the analog signal value of each channel and converts it in
a digital string (bit). Each analog signal is converted in a 16 bit word which is
serially transmitted as before described.
Then, it is possible to convert the received string in the corresponding decimal
value, considering that each value is expressed in signed integer (the most
significant bit indicates the sign: 0=positive 1=negative).
The user will must insert the decimal point as illustrated in the following tables.
Input
Binary
Hex
Decimal
Measure
Ohm
0000 0000 0000 0001
0001
1
0.1 Ohm
100 mV
0010 0001 0011 0100
2134
8500
85.00 mV
1000 mV
1111 1111 1111 1111
FFFF
-1
-0.1 mV
Tc J
1111 1000 0011 0000
F830
-2000
-200.0 °C
Examples:
Input
Decimals Format
RTD (°C)
1
+850.0
Res (Ohm)
1
+2000.0
Pot (%)
1
+100.0
Input
Decimals
Format
+/- 50 mV
3
+50.000
+/- 100 mV
2
+100.00
+/- 250 mV
2
+250.00
+/- 1000 mV
1
+1000.0
+/- 20 mA
3
+20.000
Tc J .. Tc N
1
+1200.0