7.15. Analogue output limiting
Function
The
analogue
output
works correspond with NAMUR
standard. For example the 4-20 mA type output has
3.8-20.5 mA current range.
You can limit this range. For example: let the low output
limit is 12 mA and the high output limit is 17 mA. In this
case if calculated current is lower than 12 mA or higher
than 17 mA, the output current will indicate the error state.
(See: 7.16.: Analogue output error state disabling.)
1. Type-in the low and the high output limits. (In voltage
mode the typed value is desired voltage value x2)
The figure shows the factory default settings:
Sequence of operations
7.16. Analogue output error state disabling
Function
The checked check box of the instrument disables the
output error sate. In this case the analogue output can not
generate error current, the output current remains between
the low and the high values.
(See: 7.15.: Analogue output limiting.)
1. Check the check box for disabling the output error
signal.
Sequence of operations
Содержание DT1310 Series
Страница 1: ...DT1310 xx xx Intrinsically Safe Temperature Resistance Transmitter Operating Instructions...
Страница 41: ...DT1310 xx xx 20220128 V0 41 10 2 Application example...
Страница 42: ...DT1310 xx xx 42 20220128 V0 10 3 ATEX Tan s tv ny...
Страница 43: ...DT1310 xx xx 20220128 V0 43...
Страница 44: ...DT1310 xx xx 44 20220128 V0...
Страница 45: ...DT1310 xx xx 20220128 V0 45...
Страница 46: ...DT1310 xx xx 46 20220128 V0...
Страница 47: ...DT1310 xx xx 20220128 V0 47...
Страница 48: ...DT1310 xx xx 48 20220128 V0...
Страница 49: ...DT1310 xx xx 20220128 V0 49...
Страница 50: ...DT1310 xx xx 50 20220128 V0...
Страница 51: ...DT1310 xx xx 20220128 V0 51...
Страница 52: ......