background image

 

DT1012 IP 

4

 

20221107-V0 

 

start 

1. About this document

 

 

1.1. Function

 

 

This operating instructions manual has all the information you need for 
quick set-up and safe operation of DT1012 IP. 
Please read this manual before you start setup. 
 

 

1.2. Target group

 

 

This operating instructions manual is directed to trained personnel. 
The contents of this manual should be made available to these 
personnel and put into practice by them. 
 

 

1.3. Symbolism used

 

 

Information, tip, note

 

This symbol indicates helpful additional information. 
 

 

Caution, warning, danger

 

This symbol informs you of a dangerous situation that could occur. 
Ignoring this cautionary note can impair the person and/or the 
instrument. 
 

 

List

 

The dot set in front indicates a list with no implied sequence. 
 

 

Action

 

This arrow indicates a single action. 
 

Sequence

 

Numbers set in front indicate successive steps in a procedure. 
 

 

Содержание DT1012 IP

Страница 1: ...DT1012 IP PS Temperature Resistance Potentiometer Transmitter Operating Instructions...

Страница 2: ...3 4 Setting 8 3 5 Indicator LEDs USB connector 9 3 6 Storage and transport 9 4 Mounting 10 4 1 General instructions 10 4 2 A k sz l k f bb m retei 10 4 3 Mounting 11 5 Connecting 12 5 1 Preparing the...

Страница 3: ...25 7 2 4 Resistor setting 26 7 3 Analogue output setting 27 7 4 Factory default resetting 28 7 6 Display measuring values 29 7 7 Display instrument information 29 7 8 Display USB communication inform...

Страница 4: ...f this manual should be made available to these personnel and put into practice by them 1 3 Symbolism used Information tip note This symbol indicates helpful additional information Caution warning dan...

Страница 5: ...system components through incorrect mounting or adjustment 2 4 General safety instructions The DT1012 IP is a high tech instrument requiring the strict observance of standard regulations and guideline...

Страница 6: ...t description 3 1 Delivery configuration Delivered items The scope of delivery encompasses DT1012 IP PS documentation this operating instructions Certificate mini USB 5 pin USB A cable Configuration s...

Страница 7: ...vel signal averaging etc are done via USB port The configuration program running on the PC and the USB cable are included with the instrument The transmission characteristics of the transmitter are ex...

Страница 8: ...isolation the output stage converts it into an analog current signal passive output external power supply required The instrument generates the power supply voltages required for the input side and t...

Страница 9: ...ent with a continuous green light 3 6 Storage and transport This instrument should be stored and transport in places whose climatic conditions are in accordance with chapter 10 1 Technical specificati...

Страница 10: ...hnical specification as described under the title Ambient conditions Mounting position The instruments are designed in a housing for mounting on TS 35 rail The instruments should be mounted in vertica...

Страница 11: ...ired for installation 1 In the position shown in the figure place the fixing groove of the instrument on the upper edge of the rail step 1 in figure 2 Push the lower part of the instrument towards the...

Страница 12: ...e of supply voltage Use only a screwdriver with appropriate head Take note the suitability of the connecting cable wire cross section insulation etc The wire cross section should be 0 25 1 5 mm2 You m...

Страница 13: ...2 Connecting sensor resistor potentiometer to the input The following figure shows the wiring plan connecting the sensor resistor potentiometer to the input Wiring plan connecting the sensor resistor...

Страница 14: ...cording to the wiring plan 3 Screw the terminal in 4 Check the hold of the wires in terminals by pulling on them firmly Checking the Connections Check if the cables are connected properly have you con...

Страница 15: ...sing unit Be careful the polarity of the cables Leave connection terminals 3 and 4 free 1 Loosen terminal screws 2 Insert the wire ends into the open terminals according to the wiring plan 3 Screw the...

Страница 16: ...ply Polarity is indifferent 1 Loosen terminal screws 2 Insert the wire ends into the open terminals according to the wiring plan 3 Screw the terminal in 4 Check the hold of the wires in terminals by p...

Страница 17: ...into the open terminals according to the wiring plan 3 Screw the terminal in 4 Check the hold of the wires in terminals by pulling on them firmly Checking the connections Check if the cables are conn...

Страница 18: ...he PC side 3 Make the desired settings as described in chapter 7 Setting up USB driver installation is not required It is not necessary to supply the instrument with power while making the settings Af...

Страница 19: ...ection points to be connected PI 7 PI 8 Pt 9 and Pt 10 Output type 4 20 mA passive Error indication On Analog output scaling lower value 4 mA 200 C Analog output scaling upper value 20 mA 800 C Output...

Страница 20: ...ed flashing light The sequence number of the error is given by the number of flashes 3 on indicator which indicates the power on state of the instrument with a continuous green light Error status indi...

Страница 21: ...tory as the PIC32MM exe setup program Setup steps 1 Connect the instrument to the PC with the included USB cable If you want to check the input signal then put the instrument under power If you just w...

Страница 22: ...e connected to the input of the instrument Pt temperature sensor Potentiometer Scaled potentiometer Resistor Factory default Pt temperature sensor Setup steps 1 Click the Pt Potentiometer R button in...

Страница 23: ...number you want to use 4 Select the measurement time you want to use 5 If you want to correct the error of the Pt sensor you can do it at 3 points 6 Store the settings by clicking the Write to instru...

Страница 24: ...4 Select the measurement time you want to use 5 Set the potentiometer to initial value 6 Click the 0 button 7 Set the potentiometer to final value 8 Click the 100 button 9 Store the settings by clicki...

Страница 25: ...tentiometer to initial value 6 Click the 0 button 7 Set the potentiometer to final value 8 Click the 100 button 9 Store the settings by clicking the Write to instrument button 10 Set the decimal point...

Страница 26: ...4 Resistor setting 3 Select the wire number you want to use 4 Select the measurement time you want to use 5 Store the settings by clicking the Write to instrument button 6 Close the settings window by...

Страница 27: ...above 20 mA Lower scale value Upper scale value Factory defaults see figure below Setup steps 1 Click the Analogue button in the OUTPUT field 2 In the window that appears make the necessary settings 3...

Страница 28: ...e values in the instrument exit by pressing the Exit Esc button or read the current settings from the instrument It can be advantageous if the desired setting differs only slightly from the factory se...

Страница 29: ...s there is a communication connection between the PC and the instrument in the middle of the configuration program window 7 7 Display instrument information Function The configuration program displays...

Страница 30: ...strument only receives power from the USB port Error 1 is still displayed because in this case the input module of the instrument does not receive power so the instrument perceives it as faulty Error...

Страница 31: ...count the flashes of the red indicator and find the error interpretation in chapter 7 9 Error display If you cannot eliminate the error based on the error detection result incorrect input signal inco...

Страница 32: ...it possible to open the fixing assembly figure step 2 5 Keeping the screwdriver in this position lift the instrument bottom from the bottom edge of the rail figure step 3 6 Lift the whole instrument...

Страница 33: ...rrent Output signal DC current Output ranges 4 20 mA Overload 22 5 mA Loop power 8 30 VDC Transfer characteristics Output signal error 25 C 2 C 0 1 Non linearity hysteresis 0 02 max Temperature coeffi...

Страница 34: ...horizontal rail position A version with an operating temperature range of 20 to 60 C is also available Electromagnetic compatibility EMC Accordance with the standard MSZ EN IEC 61326 1 and MSZ EN 550...

Страница 35: ...DT1012 IP 20221107 V0 35...

Страница 36: ......

Отзывы: