iBootBar
Page 11
ibootbar_v1.2x
Control
The Control panel provides the clickable buttons to cause a change of outlet condition. Once one or more outlets
are selected, click on the On, Off, or Cycle button. Cycle will perform a timed change in outlet state (either Reboot for On-
Off-On, or Cycle Off-On-Off) depending on the current state of the outlet.
The Cycle timer box allows selection of the length, in seconds of all cycle or reboot operations. Entries of 1 to 99 seconds
are valid.
The Delay timer box allows selection of the delay between turning on of each outlet whenever more than one outlet is
turned on at the same time. This can be used to prevent over-current draw on initial power up of devices. Entries of 0 to 99
seconds are valid.
The Select All and Select None buttons allow selection or de-selection of all outlets.
Refresh provides an update of the status page to display current outlet conditions.
Logout terminates the session.
Web Operation
To operate any outlet, select it with the checkbox associated with that outlet and then click the On, Off, or Cycle button as
required. The page will reload with the current status. If multiple outlets are selected, the page will refresh several times
until all outlets have completed their operation.
User Privileges
Each user can be assigned one or more outlets and groups of outlets to manage. The Web interface will only display
those outlets that the user has been authorized for.
Grouping Outlets
Outlets can be grouped into logical arrangements to provide simultaneous management. Two outlets can be grouped
together to provide control of a single server with dual redundant power supplies. When powering on multiple outlets in a
group, there will be a delay between outlets, based on the Delay Time setting. This prevents unwanted current draw. If no
delay is desired set the Delay Time to 0.