AMT58x-EC EtherCAT®
37
Synchronous with DC SYNC0
In this operating mode data is sampled and then copied into Sync
Manager buffer simultaneously at SYNC0 event generated by the
ESC capture/compare unit.
Time required for accomplishing these operations is set in object
1C33 Sync Manager input parameter
; in particular object
03 Shift
Time
(1C33hex, sub3) and object
06 Calc and Copy time
(1C33hex, sub6).
In this operating mode “Jitter” is a fundamental parameter in the
sampling of two consecutive data. The main advantage of this mode
is that there is a direct relation between the sampling instant and the
absolute time of the system; in this way, if we know the shift times of
the Slaves, we can have an exact image of the system at a given
moment (with a tolerance equal to jitter).
Description Min Typ Max
Jitter 0
100
200
µsec
Cycle Time
62,5
64000
µsec
0x1C33:02 (Cycle Time)
0x1C33:05 (Min Cycle Time)
Sync0 Event
Frame N
Frame N+1
Sync0 Event
SM3 Event
SM3 Event
0x1C33:03 (Shift Time)
0x1C33:06
(Calc & Copy)
Jitter