4.2 Ground connection
Minimize noise by connecting the shield and/or the connector
housing and/or the frame to ground. Make sure that ground is not
affected by noise. The connection point to ground can be situated
both on the device side and on user’s side. The best solution to
minimize the interference must be carried out by the user. You are
advised to provide the ground connection as close as possible to the
encoder. We suggest using the ground point provided in the cap (see
Figure, use 1 TCEI M3 x 6 cylindrical head screw with 2 tooth lock
washers).
4.3 Diagnostic LEDs
Five LEDs located in the rear side of the connection cap are
designed to show the operating or fault status of the EtherCAT®
interface.
Link/ Activity
(
yellow
)
it shows the status of the physical link and the
activity in this link
OFF
condition: port closed, link: YES, activity: N.A.
FLICKERING
condition: port open, link: YES, activity: YES
ON
condition: port open, link: YES, activity: NO
RUN (
green
)
it shows the status of the EtherCAT State
Machine (ESM)
OFF
encoder is in
INIT
status
BLINKING
encoder is in
PRE-OPERATIONAL
status
SINGLE FLASH
encoder is in
SAFE-OPERATIONAL
status
ON
encoder is in
OPERATIONAL
status
PWR (
green
)
it shows the power supply status
OFF
encoder is switched OFF
ON
encoder is switched ON
ERR (
red
)
it shows the error status
OFF no
error
FLICKERING
error on loading parameters from flash
memory at start-up
FLICKERING
encoder parameters have not been saved
correctly on flash memory
BLINKING invalid
configuration
SINGLE FLASH
local error (see ETG1000.6)
DOUBLE FLASH
watchdog timeout
ON
memory error and ESC controller not active