DKG-317 User Manual V-01.19
(01.10.2009)
- 15 -
Pgm Definition
Unit
Std Val
Description
38
Charge input alarm
-
0
0:
The charge input generates
CHARGE
warning, and does not stop the engine.
1:
The charge input generates
CHARGE
alarm,
and stops the engine.
39
Genset L-L Voltages
-
0
0:
Display genset Line to Neutral voltages,
1:
Display genset Line to Line voltages.
40
Not used
41
Not used
42
Remote Start Operation
-
0
0:
Not REMOTE START
mode, the engine
runs when the mains fail.
1:
REMOTE START
mode, the unit does not
monitor mains voltages, the engine runs when
a signal from the REMOTE START (22) comes.
43
Modem Connection
-
0
0:
No modem connection, the serial port is
connected to PC
1:
Modem connected.
44
Maintenance Period
(Engine Hours)
hours
200
The
SERVICE REQUEST
led indicator will turn
on after this quantity of engine hours from the
last service. If the period is set to ‘0’ no
SERVICE REQUEST
will be generated
depending on engine hours.
45
Maintenance Period
(Months)
month
6
The
SERVICE REQUEST
led indicator will turn
on after this amount of time from the last
service. If the period is set to ‘0’ no
SERVICE
REQUEST
will be indicated depending on time
46
Not used
47
Not used
48
Operation Password
-
0
This is the password to be entered for manual
starting of the genset. If the password is set to
0, the unit will not ask the password, else it will
ask the password if the
RUN
button is pressed.
The password may be set between 0 and 999.
49
Not used
50
Not used
51
Not used
52
Not used
53
Not used
54
Not used
55
Not used
56
Not used
57
Not used
58
Not used
59
Not used
60
Not used
61
Not used
62
Not used
63
Not used
64
Not used