background image

DKG-317 User Manual                                                                         V-01.19 

(01.10.2009)

 

 

 

 

 

 

- 15 -   

 

Pgm  Definition 

Unit 

Std Val 

Description 

38 

Charge input alarm  

0:

 The charge input generates 

CHARGE 

warning, and does not stop the engine. 

1:

 The charge input generates 

CHARGE 

alarm, 

and stops the engine. 

39 

Genset L-L Voltages 

0:

 Display genset Line to Neutral voltages, 

1:

 Display genset Line to Line voltages. 

40 

Not used 

 

 

 

41 

Not used 

 

 

 

42 

Remote Start Operation 

0:

 

Not REMOTE START

 mode, the engine 

runs when the mains fail. 

1:

 

REMOTE START

 mode, the unit does not 

monitor mains voltages, the engine runs when 
a signal from the REMOTE START (22) comes. 

43 

Modem Connection 

0: 

No modem connection, the serial port is 

connected to PC

 

1: 

Modem connected. 

44 

Maintenance Period 
(Engine Hours) 

hours 

200 

The 

SERVICE REQUEST

 led indicator will turn 

on after this quantity of engine hours from the 
last service. If the period is set to ‘0’ no 

SERVICE REQUEST

 will be generated 

depending on engine hours. 

45 

Maintenance Period 
(Months) 

month 

The 

SERVICE REQUEST

 led indicator will turn 

on after this amount of time from the last 
service. If the period is set to ‘0’ no 

SERVICE 

REQUEST

 will be indicated depending on time 

46 

Not used 

 

 

 

47 

Not used 

 

 

 

48 

Operation Password 

This is the password to be entered for manual 
starting of the genset. If the password is set to 
0, the unit will not ask the password, else it will 
ask the password if the 

RUN

 button is pressed. 

The password may be set between 0 and 999. 

49 

Not used 

 

 

 

50 

Not used 

 

 

 

51 

Not used 

 

 

 

52 

Not used 

 

 

 

53 

Not used 

 

 

 

54 

Not used 

 

 

 

55 

Not used 

 

 

 

56 

Not used 

 

 

 

57 

Not used 

 

 

 

58 

Not used 

 

 

 

59 

Not used 

 

 

 

60 

Not used 

 

 

 

61 

Not used 

 

 

 

62 

Not used 

 

 

 

63 

Not used 

 

 

 

64 

Not used 

 

 

 

 

Содержание DKG-317

Страница 1: ...wer measurement Genset power factor measurement Periodic maintenance request indicator Engine hours counter Event logging Statistical counters Field adjustable parameters RS 232 serial port Free MS Wi...

Страница 2: ...s 3 2 Digital Display 4 ALARMS AND WARNINGS 5 MODES OF OPERATION 6 OTHER FEATURES 6 1 Remote start operation 6 2 Sender type selection 6 3 Service Request Display 6 4 Engine Hour Meter 6 5 Modem conne...

Страница 3: ...the retaining steel spring and connectors from the unit then pass the unit through the mounting opening The unit will be maintained in its position by the steel spring Engine body must be grounded fo...

Страница 4: ...porate appropriate short circuit backup protection e g a fuse or circuit breaker of High Breaking Capacity HBC at least 1500A 6 Use cables of adequate current carrying capacity at least 0 75mm 2 and t...

Страница 5: ...table from a list 19 START RELAY Output 10A 28VDC This relay controls the engine cranking 20 FUEL RELAY Output 10A 28VDC This relay is used for fuel solenoid control It is internally connected to term...

Страница 6: ...hours or time duration after previous service has elapsed ALARM GROUP Red If a fault condition resulting to the engine shutdown has occurred the related alarm led turns on steadily If a warning condi...

Страница 7: ...generator phase to neutral voltages UV VW WU generator phase to phase voltages If the service counters group is displayed then this display will show the counter name In programming mode it displays P...

Страница 8: ...med HIGH TEMPERATURE Set if a signal is detected at the High Temperature Switch input or the coolant temperature value measured from the sender is above the programmed limit Warning P_017 and alarm P_...

Страница 9: ...ter P_042 is set to 1 then the unit will enter to the Remote Start operation In this mode the engine will run and stop with the Remote Start signal It is also necessary to set the program parameter P_...

Страница 10: ...ing engine hours and the remaining time limit are kept stored in a non volatile memory and are not modified by power supply failures The remaining time and engine hours to service may be checked via t...

Страница 11: ...0 CASECOM USB TO SERIAL CONVERTER MODEL RS 01 7 EVENT LOGGING The unit keeps records of the last 12 events in order to supply information for the service personal The events are stored in a circular m...

Страница 12: ...er failures To exit the program mode press one of the mode selection keys If no button is pressed during 1 minute the program mode will be cancelled automatically Pgm Definition Unit Std Val Descripti...

Страница 13: ...High Battery Voltage Alarm V 33 0 If the battery voltage goes over this limit this will generate a BATTERY alarm and the engine will stop 15 Low Oil Pressure Warning Bar 1 5 If the oil pressure measu...

Страница 14: ...limits P_008 P_011 and SPEED FAULT alarm occurs 25 Not used 26 Preheat timer sec 1 This is the time after the fuel solenoid is energized and before the genset is started During this period the PREHEA...

Страница 15: ...ngine Hours hours 200 The SERVICE REQUEST led indicator will turn on after this quantity of engine hours from the last service If the period is set to 0 no SERVICE REQUEST will be generated depending...

Страница 16: ...n 22 74 RELAY 10 function 23 75 RELAY 11 function 24 76 RELAY 12 function 25 77 RELAY 13 function 26 78 RELAY 14 function 27 79 RELAY 15 function 28 80 RELAY 16 function 29 81 RELAY 17 function 30 82...

Страница 17: ...e 1 Battery positive 88 Response delay 0 0 No delay 1 Delayed 4sec HIGH TEMPERATURE SWITCH INPUT Pgm Description Std 89 Operation 0 0 Alarm the engine stops and horn relay operates 2 Warning the horn...

Страница 18: ...relay operates 2 Warning the horn relay operates 3 No operation 108 Fault monitoring 0 0 Always 1 After holdoff timer 2 When mains present 109 Latching 0 0 Non latching 1 Latching 110 Contact type 0 0...

Страница 19: ...t type 0 0 Normally open 1 Normally closed 129 Switching 0 0 Battery negative 1 Battery positive 130 Response delay 0 0 No delay 1 Delayed 4sec Parameters from P_131 to P_142 define the ohm bar charac...

Страница 20: ...red as 0 An example table is given below The sensor characteristics used in this table are 38 C 342 ohms 82 C 71 ohms 104 C 40 ohms 121 C 30 ohms Pgm Description Unit Value 143 Point_1 resistor ohm 30...

Страница 21: ...the Amp readings are correct Current transformers are not connected to the correct inputs or some of the CTs are connected with reverse polarity Determine the correct connections of each individual C...

Страница 22: ...between BATTERY and charging alternator D terminal The normally closed contact of the relay will be connected serially to the unit s START output So the starting will also be removed when the D pulls...

Страница 23: ...Internally connected to battery positive via 4700 ohm resistor Analog inputs Resistor input 0 to 5000 ohms connected to the battery negative Sources 10 mA when closed to battery negative Measurement...

Страница 24: ...DKG 317 User Manual V 01 19 01 10 2009 24 14 CONNECTION DIAGRAM...

Отзывы: