DKG-317 User Manual V-01.19
(01.10.2009)
- 16 -
The parameters from P_065 to P_082 define the functions of relay outputs. The unit has 4 relay
outputs and 2 of them have programmable functions. The fixed function relays are Fuel and Start.
The relays may be extended up to 20 using
Relay Extension Modules
. RELAY-1 and RELAY-2
with programmable functions are inside the unit. Other relays are in the optional Extension Modules.
The function of a programmable relay output may be selected from the below list.
RELAY FUNCT
İ
ON LIST
Pgm
Description
Std
65
RELAY-1 function
01
66
RELAY-2 function
03
67
RELAY-3 function
16
68
RELAY-4 function
17
69
RELAY-5 function
18
70
RELAY-6 function
19
71
RELAY-7 function
20
72
RELAY-8 function
21
73
RELAY-9 function
22
74
RELAY-10 function
23
75
RELAY-11 function
24
76
RELAY-12 function
25
77
RELAY-13 function
26
78
RELAY-14 function
27
79
RELAY-15 function
28
80
RELAY-16 function
29
81
RELAY-17 function
30
82
RELAY-18 function
31
00
Fuel
01
Horn
02
Start
03
Stop
04
-
05
-
06
Choke
07
Preheat
08
Alarm
09
Warning
10
Alarm+Warning
11
Automatic ready
12
-
13
-
14
-
15
Genset ready
16
Oil switch alarm
17
Temp switch alarm
18
Level switch alarm
19
Rectifier alarm
20
Emerg.Stop alarm
21
Spare-1 Alarm
22
Spare-2 Alarm
23
-
24
Oil sender alarm
25
Temp sender alarm
26
Speed alarm
27
Start fail alarm
28
Charge alarm
29
Overload alarm
30
Voltage alarm
31
Battery High alarm
32
Oil switch warning
33
Temp switch warn.
34
Level switch warn.
35
Rectifier warning
36
Emerg Stop warn.
37
Spare-1 warning
38
Spare-2 warning
39
-
40
Oil sender warning
41
Temp sender warn.
42
Speed warning
43
Stop Fail warning
44
Charge warning
45
Battery low warning
46
-
47
Battery high warn.